Compressor models – Liebert Precision Cooling System DS User Manual

Page 104

Advertising
background image

Piping Schematics

94

Figure 69 Primary connection locations—downflow, air-Cooled, 53-77kW (15-22 ton), semi-hermetic

compressor models

Point

Description

X

inches (mm)

Y

inches (mm)

Connection Size / Opening

inches (mm)

R

Refrigerant Access

82-3/4 (2102)

13-7/8 (352)

16-7/16 x 4 (418 x 102)

53kW (15ton) / 70 & 77kW (20 & 22ton)

L1

Liquid Line System 1

97 (2464)

16-7/8 (428)

1/2 / 5/8 Cu Sweat

L2

Liquid Line System 2

93-5/16 (2370)

16-7/8 (428)

1/2 / 5/8 Cu Sweat

G1

Hot Gas Discharge 1

90-5/8 (2302)

16-5/8 (422)

7/8 / 1-1/8 Cu Sweat

G2

Hot Gas Discharge 2

88 (2235)

16-5/8 (422)

7/8 / 1-1/8 Cu Sweat

CD

Condensate Drain *

69-1/4 (1759)

30 (762)

3/4 FPT

W/ Optional Pump

69-1/4 (1759)

30 (762)

1/2 Cu Sweat

HUM

Humidifier Supply Line

76-1/2 (1943)

29 (736)

1/4 Cu Sweat

ECS**

Econ-O-Coil Supply

78-5/8 (1997)

22-1/4 (565)

2-1/8 Cu Sweat

ECR**

Econ-O-Coil Return

72 (1829)

29 (737)

2-1/8 Cu Sweat

HS

Hot Water Reheat Supply

Consult Factory

HR

Hot Water Reheat Return

Consult Factory

E1

Electrical Connection (High Volt)

78-1/2 (1994)

31-1/8 (790)

2-1/2

E2

Electrical Connection (High Volt)

75-3/8 (1915)

31-1/8 (790)

2-1/2

LV1

Electrical Connection (Low Volt)

1-7/8 (48)

28-1/2 (724)

7/8

LV2

Electrical Connection (Low Volt)

1-7/8 (48)

30-1/4 (768)

7/8

LV3

Electrical Connection (Low Volt)

1-7/8 (48)

32 (813)

7/8

B1

Blower Outlet (15 x 15)

23-1/8 (587)

18-1/16 (459)

18-3/4 x 16-1/16 (476 x 408)

Blower Outlet (15 x 11)

27-3/4 (705)

18-1/16 (459)

14-3/4 x 16-1/16 (375 x 408)

B2

Blower Outlet (15 x 15)

50-3/8 (1280)

18-1/16 (459)

18-3/4 x 16-1/16 (476 x 408)

Blower Outlet (15 x 11)

54-3/8 (1381)

18-1/16 (459)

14-3/4 x 16-1/16 (375 x 408)

* Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305mm). All units contain a factory-installed condensate trap. Do

not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.

** Supplied on Dual-Cool systems only (4-pipe system)

Section A-A

Front View

16-1/16"

(408 mm)

A

A

X

Y

O

35"

(889mm)

All dimensions
from rear corner
of unit including
panels

Tolerance on all
piping dimensions
is ± 1/2" (13mm)

109"

(2769mm)

Front of Unit

Note: Drawing not to scale

DPN000928
Rev. 2

4" (102mm)

LV3

LV2

LV1

ECS

HUM

CD

ECR

E1 E2

B2

16-7/16"

(418mm)

L1

L2

G1 G2

Blower

Outlet

B1

Blower

Outlet

R