Figure 9, Semi-hermetic compressor models, Table 6 – Liebert Precision Cooling System DS User Manual

Page 24

Advertising
background image

Liebert DS Dimensions and Weights

14

Figure 9

Cabinet and floor planning dimensions—downflow, air-cooled, 53-77kW (15-22 ton),
semi-hermetic compressor models

Table 6

Weights for downflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressor models

Model

Dry Weight, lb (kg) Approximate

053

070

077

Air-Cooled

2350 (1069)

2400 (1091)

2450 (1114)

Dual-Cool

2530 (1150)

2580 (1173)

2630 (1196)

33"

(838mm)

35"

(889mm)

109"

(2769mm)

76"

(1930mm)

2"

(51mm)

108"

(2743mm)

34"

(864mm)

Shaded area indicates a
recommended minimum
clearance for component
access.

15"

(381mm)

3/4"

(19mm)

24-3/8"

(619mm)

80"

(2032mm)

Second Refrigerant
Piping Entrance

Air Inlet Opening

Opening

Opening

Bezels

Secondary Entrance
Low Volt Connections

Minimum required

for filter replacement

Secondary Entrance
High Volt Connection(s)

Top View

Front View

Notes: Filters are accessible

through top of unit only.

Downflow

electrical

connections can be made

from top or bottom of unit.

DPN000924

Rev. 2

Advertising