Simplified installation option 1, Return/return method) – Lifebreath CONTROLAIR 15 200MAX User Manual

Page 22

Advertising
background image

22

Simplified Installation

Option 1

(Return/Return Method)

Note: Option 1 is the preferred / recommended method
when doing a simplified installation.

Example diagram only - duct configuration
may change depending on model

*Unit is normally balanced on HIGH speed
with furnace blower ON.

RETURN AIR

DIRECT CONNECTION of both the HRV/ERV SUPPLY AIR STREAM and

EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN

40" (1m) MINIMUM

Outdoors

Cool Air

Return

NOTES:

1. Furnace blower may be required to operate when ventilation from HRV/ERV is required.
The furnace should be set to run continuously or interlocked with HRV/ERV.
2. A minimum separation of 40 inches (1 m) is required between the two direct connections.
3. The exhaust air connection should be upstream of the supply air connection to prevent
exhausting any fresh air.
4. Weatherhood arrangement is for drawing purposes only. Six feet (2 m) minimum separation required.
Eighteen inches (460 mm) above grade minimum.
5. Due to the differences in pressure between the HRV/ERV and the equipment it is being
connected to, the HRV/ERV's airflow must be confirmed on site, using the balancing
procedure found in the installation manual.

3’ min.

recommended

Forced Air

Furnace