Technical Bulletin

When using the ControlAir 15 relay contacts to initiate blower operation on a
furnace, certain thermostats will initiate the outdoor cooling condenser when
R and G are closed.

Use this wiring configuration to stop the ControlAir15 relay contacts from initializing
the condenser unit. This problem can occur at the thermostat because the

Y

terminal

is connected to the

G

terminal internal to the stat. When

R

and

G

are closed at the fur-

nace (by dehumidistat or relay) 24 Volts is sent to

G

at thermostat. 24 Volts is then

sent through

Y

which will initiate outdoor condenser.

R G W Y C

R G W Y

Furnace

Thermostat

T9

T10

T11

T12

T13

T14

T5

T4

T3

GROUND

HIGH VOLTAGE

12V LOW VOLTAGE

FIELD INSTALLED

LEGEND

LOW VOLTAGE

P3

FAN O/P

NEUTRAL

THERMIST0R

P4

P1

SEL1

SEL2

FOR R-2000

REMOVE SEL1

TO DISABLE

RECIRCULATION

REMOVE SEL2

DRY

CONTACT

T7

T8

T1

T2

T6

N/C

COMMON

N/O

T15

MICRO PROCESSOR BOARD

DEHUMIDISTAT

P2

P5

INTERNAL

WARNING

750 ma

MAX FUSE

2

1

P6

LINE

CHASSIS

CONTROLAIR 15

YEL

GRN

ORN

RED

BLK

TB-102-NE