Model maxtop, Performance, Engineering data – Lifebreath MAXTOP User Manual

Page 11: Dimensions maxtop

Advertising
background image

11

ENGINEERING DATA

THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two
airstreams.
It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor.
5 speed fan operation. 120 VAC, 1.4 Amps.

FILTERS - Washable air filters in exhaust and supply air streams.

MOUNTING THE HRV - Four threaded inserts at corners of case designed
to accept four reinforced polyester straps that are supplied with the unit.
DEFROST
Recirculating damper defrost system.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion
resistance. Insulated to prevent exterior condensation. Drain connections 2
- 1/2" (12 mm) OD.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode, 20 ON/40
Recirculation mode, Recirculation mode (each mode has 5 speeds). Control
pad can be removed from HRV and remotely mounted.

Weight 87 lbs. (39.5 kg) Shipping Weight 89 lbs. (40.5 kg)

TOP VIEW

SIDE VIEW

25 1/2 "

(648 mm)

26 1/2"

(673 mm)

22 1/2"

(572 mm)

FRONT VIEW

ALL DUCT CONNECTIONS
ARE 6" (150 mm)

18"

(457 mm)

7 1/2"

(191 mm)

SUPPLY OF
FRESH AIR

FRESH AIR
SUPPLY
TO BUILDING

STALE AIR
RETURN FROM
BUILDING

STALE AIR
EXHAUST

DRAIN
CONNECTION

CONTROLS

*Service Clearance
25" (635 mm)

OPTIONS
99-104

Digital Electronic Timer - 20/40/60 min.

99-109

Air Sentry™ Air Quality Monitor designed to accept
remotely mounted Control Pad

99-250

Ventilation Dehumidistat - Dehumidistat designed to
accept remotely mounted Control Pad

99-163

Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6”
(150mm)

99-164

Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 6”
(150mm)

99-186

Weatherhoods, Two - 6” (150mm) c/w 1/4” (6mm) mesh
screen

WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5
year replacement parts warranty.

TI-100-NE

0107

Model MAXTOP

All units conform to
CSA and UL standards.

DIMENSIONS MAXTOP

inches (mm)

Date: ___________________________________________

Tag: _____________________Qty:___________________

Project: _________________________________________

Engineer: _______________________________________

Contractor: ______________________________________

Supplier: ________________________________________

Quote#: _________________________________________

Submitted by: ____________________________________

*Sensible Efficiency – thermal **Latent Efficiency – moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams
Efficiency – takes into account all power inputs

Performance

(HVI certified)

Net supply air flow in cfm (L/s) against external static pressure

E.S.P

(external static pressure)

[cfm (L/s)]

@ 0.1" (25 Pa)

196 (93)

@ 0.2" (50 Pa)

188 (89)

@ 0.3" (75 Pa)

178 (84)

@ 0.4" (100 Pa)

165 (78)

@ 0.5" (125 Pa)

149 (70)

@ 0.6" (150 Pa)

131 (62)

@ 0.7" (175 Pa)

109 (51)

@ 0.8" (200 Pa)

79 (37)

@ 0.9" (225 Pa)

48 (23)

Max. Temperature Recovery

83%

Sensible Effectiveness
@ 65 cfm (31 L/s)

32°F (0°C)

80%

*Sensible Efficiency
@ 65 cfm (31 L/s)

32°F (0°C)

69%

*Sensible Efficiency
@ 67 cfm (31 L/s)

-13°F (-25°C)

70%

VAC @ 60HZ

120

WATTS / Low speed.

74

WATTS / High speed

164

Amp rating

1.4

1

2

3

4

5

20

40

60

80

100

120

140

160

180

200

220

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

Static Pressure (in w.g.)

A

ir

Flow (

c

fm

)

5 - High Speed
*4 - Medium High Speed
*3 - Medium Speed
*2 - Medium Low Speed
*1 - Low speed
* Manufacturers Data

Advertising
This manual is related to the following products: