Optional dehumidistat, Or dehumidistat 24 volt relay, Interface relay – Lifebreath AH80BHW User Manual

Page 20

Advertising
background image

20

When using a Dehumidistat or Interface Relay to initiate high speed blower operation on a
furnace, certain thermostats will initiate the outdoor cooling condenser when R and G are closed.

Use this wiring configuration to stop the Dehumidistat from initializing the condenser unit. This
problem can occur at the thermostat because the Y terminal is connected to the G terminal
internal to the stat. When R and G are closed at the furnace (by dehumidistat or relay) 24 Volts
is sent to G at thermostat. 24 Volts is then sent through Y which will initiate outdoor condenser.
The relay will isolate this problem.

NOTE: This problem does not occur with all thermostats, therefore it is important to fully

commission the installation to determine if this relay configuration is required.

R G W Y C

R G W Y

Furnace

T-stat

COM

or Dehumidistat

24 Volt

Relay

NO

Interface Relay

NC

TB-102

1099

Optional Dehumidistat

An optional dehumidistat can be connected to the furnace to help eliminate

excessive moisture during the heating season. When the dehumidistat

senses moisture in excess of the control setpoint, the blower will be

overridden into high speed. This will increase the ventilation airflow and

create a dehumidification affect. Typical settings are between 30-40 during

the winter and OFF for all other seasons.

The dehumidistat will connect to R&G terminals on the furnace.

Note: Do not use dehumidistat for hot southern climates.

Dehumidistat

Setting Relative to

Outside Conditions

WINTER

:

Set deh

umidista

t

betwee

n 30% t

o 40%.

If home

is too d

ry,

adjust t

o highe

r settin

g.

If home

is too h

umid,

adjust t

o lower

setting

.

SUMME

R:

Set deh

umidist

at

to OFF.

Part # 99-130W

Advertising
This manual is related to the following products: