System commissioning, Water pump performance specifications, The air filter is in place – Lifebreath AH80BHW User Manual

Page 24: Hot water is available to the furnace, The drain valve for the heating loop is closed, Electrical power is available at the furnace

Advertising
background image

24

Water Pump Performance Specifications

16

14

12

10

8

6

4

2

0

Capacity on U.S. gpm

Model 40

1 2 4 6 8 10 12

Total Head in Feet

Model 60

1 2 4 6 8 10 12 14 16 18

20

16

14

12

10

8

6

4

2

0

Capacity on U.S. gpm

Total Head in Feet

This section of the manual is designed to be used
with the “Commissioning of Integrated Combo
System” worksheet. The worksheet is designed to
guide you through the start-up process in a logi-
cal, step by step method which should minimize
the work and time involved in having the system
meet the designed parameters.

The following conditions are assumed:

The air filter is in place

All supply diffusers and return grilles are
fully open and unrestricte

Hot water is available to the furnace

The drain valve for the heating loop is
closed

The shut off valves for the heating loop are

fully open

The throttling valve for the heating loop (if
applicable), is fully opened

Electrical power is available at the furnace

The return air temperature from the house
is approximately 70˚F (21˚C)

System Commissioning