Installation – Vanguard Heating VN18A User Manual

Page 12

Advertising
background image

www.desatech.com

113052-01A

12

Tee Pipe Cap
Joint Nipple

CAUTION: Use only new,

black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of
large enough diameter to allow
proper gas volume to heater. If
pipe is too small, undue loss of
volume will occur.

Typical Inlet Pipe Diameters

VN18A, VN18TA, VP16A, VP16TA, and

VP16ITA - 3/8" or greater

VN30A, VN30TA, VP26A, VP26TA, and

VP22ITA - 1/2" or greater

Installation must include equipment shutoff valve,
union, and plugged 1/8" NPT tap. Locate NPT tap
within reach for test gauge hook up. NPT tap must
be upstream from heater (see Figure 15).

IMPORTANT:

Install an equipment shutoff valve

in an accessible location. The equipment shutoff
valve is for turning on or shutting off the gas to
the appliance.

Apply pipe joint sealant lightly to male NPT
threads. This will prevent excess sealant from go-
ing into pipe. Excess sealant in pipe could result
in clogged heater valves.

WARNING: Use pipe joint

sealant that is resistant to liquid
petroleum (LP) gas.

Install sediment trap in supply line as shown in
Figure 15. Locate sediment trap where it is within
reach for cleaning. Locate sediment trap where
trapped matter is not likely to freeze. A sediment
trap traps moisture and contaminants. This keeps
them from going into heater controls. If sediment
trap is not installed or is installed wrong, heater
may not run properly.

IMPORTANT:

Hold the pressure regulator with

wrench when connecting it to gas piping and/or
fittings. Do not over tighten pipe connection to
regulator. The regulator body could be damaged.

INSTALLATION

Continued

Tee Joint

Reducer
Bushing to
1/8" NPT

1/8" NPT
Plug Tap

* A CSA design-certified equipment shutoff valve
with 1/8" NPT tap is an acceptable alternative to
test gauge connection. Purchase the optional CSA
design-certified equipment shutoff valve from your
dealer. See Accessories, page 33.

Figure 15 - Gas Connection

Pressure
Regulator

Test Gauge Connection*

Heater
Cabinet

Sediment Trap

Equipment
Shutoff
Valve *

3"
Min.

Natural Gas

From Gas
Meter (7" W.C.
to 10.5" W.C.
Pressure)

Propane/LP

From External
Regulator
(11" W.C. to 14"
W.C. Pressure)

Regulator
Bracket

Ground
Joint
Union

3/8" NPT
Pipe
Nipple

CHECKING GAS CONNECTIONS

WARNING: Test all gas pip-

ing and connections, internal
and external to unit, for leaks
after installing or servicing. Cor-
rect all leaks at once.

WARNING: Never use an

open flame to check for a leak.
Apply a noncorrosive leak de-
tection fluid to all joints. Bubbles
forming show a leak. Correct all
leaks at once.

CAUTION: For propane/LP

gas, make sure external regula-
tor has been installed between
propane/LP supply and heater.
See guidelines under

Connect-

ing to Gas Supply, page 11.