Setting the duo limit switching (option), 2 setting direction open (white section), 3 checking the duo limit switches – AUMA Electric multi-turn actuators SA 07.1 - 16.1_SAR 07.1 - 16.1 MATIC AM 01.1 - 02.1 User Manual

Page 24: Duo limit switching 24

Advertising
background image

13.

Setting the DUO limit switching (option)

Any application can be switched on or off via the two intermediate position switches.

For setting, the switching point (intermediate position) must be
approached from the same direction as later during
electrical operation.

13.1 Setting direction CLOSE (black section)

.

Move valve to desired intermediate position.

.

Press down

and turn setting spindle G (figure P-2) with a flat blade screw driver

in direction of arrow, while observing pointer H.
While a ratchet is felt and heard, the pointer H moves 90° every time.
When pointer H is 90° from mark C, continue turning slowly. When pointer H has
reached the mark C, stop turning and release setting spindle. If you override the trip-
ping point inadvertently (ratchet is heard after the pointer has rotated), continue turn-
ing the setting spindle in the same direction and repeat setting process.

13.2 Setting direction OPEN (white section)

.

Move valve to desired intermediate position.

.

Press down

and turn setting spindle K (figure P-2) with a flat blade screw driver

in direction of arrow, while observing pointer L.
While a ratchet is felt and heard, the pointer L moves 90° every time.
When pointer L is 90° from mark F, continue turning slowly. When pointer L has
reached the mark F, stop turning and release setting spindle. If you override the trip-
ping point inadvertently (ratchet is heard after the pointer has rotated), continue turn-
ing the setting spindle in the same direction and repeat setting process.

13.3 Checking the DUO limit switches

The red test buttons T and P (figure P-2) are used for manual operation of the
DUO limit switches.

.

Turning T in direction of the arrow TSC (DSR) triggers DUO limit switch CLOSED.
The torque switch CLOSED is actuated at the same time.

.

Turning P in direction of the arrow TSO (DÖL) triggers DUO limit switch OPEN.
The torque switch OPEN is actuated at the same time.

.

After checking the switches, the fault (red indication light) has to be reset using the
OPEN or CLOSE push buttons of the local controls for operation in the opposite direc-
tion.

24

Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1 / AM 02.1

Operation instructions