BASIC OPERATIONS

4-1

Chapter 4

Chapter4 BASIC

OPERATIONS

This chapter describes the basic operations of SafetyOne. Make proper use of the
SafetyOne by thoroughly familiarizing yourself with basic operations and functions.

Internal states

The SafetyOne operates in five internal states, as shown in Table 4.1.
The LED display and output status for each state are shown in Table 4.2.1and 4.2.2.
Table 4.1 Internal states

State

Description

Initial

Initial processing is performed immediately after power is supplied to the SafetyOne.
The internal circuits are checked and the LEDs show operation confirmation (blinking)
for 6 seconds (approx)..

Run

The SafetyOne is under normal operation. Logic processing continues without failures
or wiring errors. (Refer to "Chapter 5 LOGIC" for details.)

Configuration

A logic or OFF-delay timer value is being configured.
Configuration enables the logic and OFF-delay timer value. When completed, the
SafetyOne changes to the Run state. (Refer to "Logic configuration" and "Timer
configuration" in this chapter for details.)

Protection

An input monitor error has occurred with dual channel input, EDM input, or muting
input. When the problem is removed, the SafetyOne changes to Run state. (Refer to
"Canceling the Protection state" in this chapter for details.)

Stop

A failure or error has occurred with an external device or internal circuit. When the
problem is removed and the power is turned on, Stop state is cleared. (Refer to
"Canceling the Stop state" in this chapter for details.)

Table 4.2.1 LED display and output status for each state

(When safety outputs are dual channel outputs)

Safety
output

Solenoid/
lamp output

Monitor output

State

Logic
LED

Error
LED

Timer
LED

Y0…Y3

Y17,Y20

Y4…Y13

Y14

Y15

Y16

Initial (1)

(1)

(1)

OFF

OFF

OFF

ON

ON

OFF

Run

Logic #

Blank

Selected Value

(2)

(2)

(2)

OFF

OFF

ON

Configuration (3)

“C” (3)

OFF

OFF

OFF

OFF

ON

OFF

Protection

Logic #

“1”

Selected Value

OFF

(6)

OFF

(4) □

OFF

ON

OFF

Stop Blank

(5)

Blank □

OFF

OFF

(4) ■

ON

ON

or

OFF

OFF

Table 4.2.2 LED display and output status for each state

(When safety outputs are single channel outputs)

Safety
output

Monitor output

State

Logic
LED

Error
LED

Timer
LED

Y0…Y3

Y4…Y13, Y17, Y20

Y14

Y15

Y16

Initial (1)

(1)

(1)

OFF

OFF

ON

ON

OFF

Run

Logic #

Blank

Selected Value

(2)

(2)

OFF

OFF

ON

Configuration (3)

“C” (3)

OFF

OFF

OFF

ON

OFF

Protection

Logic #

“1”

Selected Value

OFF

(6) (4)

OFF

ON

OFF

Stop Blank

(5)

Blank □

OFF

(4)

ON

ON

or

OFF

OFF