2 performance specifications, 1 general specifications -2 – Proface GP4100 - 3.4 Compact HMIs" User Manual

Page 33

Advertising
background image

GP-4100 Series Hardware Manual

3-4

3.1.2

Performance Specifications

„Performance Specifications

GP4104

GP4105

GP4106

GP4107

Application
Memory

*1

*1

Capacity available for user application.

FLASH EPROM 2.2 MB

Logic Program Area

None

Font Area

None

Data Backup

FLASH EPROM 128KB

*2

*2

Stores the Alarm History Data, Recipe Data, and Brightness/Contrast Control Settings.

Variable Area

None

Clock Accuracy

Uses the clock of an external device

*3

*3

Set up the “Clock Updates“ feature with the Editor software. Please refer to the GP-Pro EX
Reference Manual “Common” - “Clock Update Settings” for details.

Interface

Serial (COM1)

RS-232C
Asynchronous
Transmission
Data Length: 7
or 8 bit
Parity: none,
Odd or Even
Stop Bit: 1 or 2
bit
Data
Transmission
Speed: 2,400
bps to 115.2
kbps
Connector: 2-
piece terminal
block 9 pin

RS-422/485,
Asynchronous
Transmission
Data Length: 7
or 8 bit
Parity: none,
Odd or Even
Stop Bit: 1 or 2
bit
Data
Transmission
Speed: 2,400
bps to 115.2
kbps
Connector: 2-
piece terminal
block 9 pin

RS-485
(isolation)
Asynchronous
Transmission
Data Length: 7
or 8 bit
Parity: none,
Odd or Even
Stop Bit: 1 or 2
bit
Data
Transmission
Speed: 2,400
bps to 115.2
kbps, 187.5
kbps (MPI)
Connector: D-
Sub9 (socket)

Ethernet

IEEE802.3u,
10BASE-T/
100BASE-TX,
Connector:
Modular jack
(RJ-45) x 1

USB
(Type-A)

*4

*4

If connecting a bar code reader to the GP, be sure to supply power from an external source
(such as a self-powered hub). If you supply power from the GP, the GP may reset itself
because the GP cannot supply enough power.

Conforms to USB2.0 (TYPE-A) x 1

Power Supply Voltage: DC5V ±5%

Communication Distance: 5 m or less

USB (mini-B)

Conforms to USB2.0 (mini-B) x 1

Communication Distance: 5 m or less