3 enabling/disabling self tests, 5 alarm relay, Section 5.4.3 – LumaSense Technologies 3434i SF6 Leak Detector User Manual

Page 67

Advertising
background image

Chapter 5

______________________________________________________________________

_____________________________________________________________________________

BE6028-14

3434i SF6 Leak Detector

LumaSense Technologies A/S

Page 67 of 191

1. Press SET-UP.

2. Press S3 S1 S1 S2 .

The following screen picture appears:


3. To change the volume, press

¿

.

4. Use the direction push-buttons to enter the correct volume. If you

make a mistake, press S1 to revert back to the original volume.

5. Press

¿

to accept volume.

6. Press SET-UP to exit the set-up function.

5.4.3

Enabling/Disabling Self Tests

If you do not wish the Monitor to perform regular self-tests, including

the hardware test on power-up you can disable it.

1. Press SET-UP S3 S1 S1 S3

2. Press S1, the Monitor no longer performs the hardware test as

part of its self-testing procedure during any kind of reset.

3. Press SET-UP to exit the set-up function.

5.5 Alarm Relay

Two alarm relays are built into the alarm relay socket on the

back panel of the Monitor. The function of the pins in this female

connector are shown in

Fig.5.2

. The two alarm relays can be

connected to a variety of either audio (for example, a siren)

SOUND VOLUME 1

PRESS ENTER TO CHANGE VALUE

REGULAR SELF - TESTS ?

NO YES