4 Channel Relay Card

Four Channel Relay Card Instruction Manual

Rev.1.2

Page 4 of 8

Table 1 Examples of Alarm Configuration

S W 1 2
60 %

OFF

OFF

X

OFF

OFF

OFF

OFF

S W 1 1
55%

OFF

OFF

X

OFF

OFF

OFF

OFF

S W 1 0
50 %

O N

OFF

X

O N

OFF

OFF

OFF

S W 9
45%

OFF

OFF

X

OFF

OFF

OFF

OFF

S W 8
40 %

OFF

OFF

X

OFF

OFF

OFF

OFF

S W 7
35%

OFF

O N

X

OFF

O N

OFF

O N

S W 6
30 %

OFF

OFF

X

OFF

OFF

OFF

OFF

S W 5
2 5%

OFF

O N

X

OFF

OFF

OFF

O N

S W 4
2 0 %

OFF

OFF

X

O N

OFF

OFF

OFF

S W 3
1 5%

O N

O N

X

OFF

OFF

OFF

O N

S W 2
1 0 %

O N

OFF

X

OFF

OFF

OFF

O N

S W 1
E N

O N

O N

OFF

O N

O N

O N

O N

M eaning

Enabled,

ALM1=10%,
ALM2=15%,

ALM3=50%

Enabled,

ALM1=15%,
ALM2=25%,

ALM3=35%

Disabled,

input

ignored

Enabled,

ALM1=20%,
ALM2=50%,

ALM3 not used

Enabled,

ALM1=35%,

ALM2 not used
ALM3 not used

Enabled,

no alarms

enabled,

fault relay is

activated

Enabled,

too many

levels

enabled,

fault relay is

activated

The 4-20mA input from ‘Enabled’ channels is monitored by the controller. If the input on a channel is less
than 2.2mA, the fault relay is activated. The fault relay is also activated if a channel is enabled, but no alarm
levels or too many alarm levels have been enabled.

If a channel is disabled, its 4-20mA input is not

monitored.

3.2

Alarm Configurations

The alarm relays for alarms 1, 2, and 3 each have a DIP switch bank with three switches that are used to
configure the relays.

The Fault relay has a DIP switch with one active switch that controls the fault

configuration. Alarms 1, 2, and 3 can be configured as Silencable, Non-Silencable, Latching, Non-Latching,
Energized, or Non-Energized. The Fault relay can only be configured as Latching or Non-Latching. Each
relay provides the customer with a set of dry contacts. The contacts are Common, Normally Open, and
Normally Closed, labeled ‘C’, ‘NO’, and ‘NC’ respectively.

ON

OFF

FAULT

ALARM 1

Silencable

Latching

Energized

Latching

Not Used

ON

OFF

ALARM 2

Silencable
Latching
Energized

ALARM 3

Silencable
Latching
Energized

Figure 3 Alarm Configuration DIP Switches