Checking power input voltage – Innotech Maxim User Manual

Page 46

Advertising
background image

MAXIM Installation Instructions

Page 46

© Mass Electronics Pty Ltd 2011

Edition 2.0 dated 20/11/2013

1 2

24V

DIGITAL CONTROLLER

24V

TRANSFORMER

EARTH

Circuit Breaker

OFF

DMM

From 240V

suply

24V

0V

5-2.2.1 Checking Power Inputs

The power inputs must be inspected to ensure that the supplied voltage is within the specifications

of the particular controller, as illustrated in Figure 5-1 below. In cases where a DC power source is

utilised, correct polarity must be verified, and the 0V terminal must be connected to ground. When

an AC power source is utilised you must verify that the AC Neutral wire is properly earthed and

connected to the 0V terminal on the particular controller.

You can check and verify correct operation of the 24VAC and 24V DC power supply inputs by

following the steps below:

1. Verify that the main power and the circuit breaker are both OFF.

2. Verify that the resistance between the main earth link of the enclosure and Terminal 2 of the

controller measures 3Ω or less.

3. Connect the red (+) test lead of your Digital Multi Meter (DMM) to the line voltage side (24V from

the transformer) of the circuit breaker, and the black (–) lead of the DMM to the 0V terminal of

the transformer.

4. Verify that the DMM is set to the proper range to measure 24V. In most cases the AUTO setting

will suit most measurements.

5. Ensuring that the circuit breaker remains OFF, now only turn the 240V supply power ON and

observe the reading on the DMM. The measured voltage should be 24V within ±10%. Please

note that the DMM must be set correctly to measure either AC or DC voltage depending on the

type of power source connected to the controller.

6. You can now turn the 240V supply power OFF and disconnect the DMM.

7. The above steps can be repeated to check the power inputs on other controllers.

Figure 5-1:  Checking Power Input Voltage

Advertising