Commissioning menu, A-4 vavmax settings a-5 commissioning, A-4 vavmax settings – Innotech Maxim User Manual

Page 58: A-5 commissioning

Advertising
background image

MAXIM Installation Instructions

Page 58

© Mass Electronics Pty Ltd 2011

Edition 2.0 dated 20/11/2013

A-4 VAVMax Settings

Configuring a VAVMax controller requires a number of parameters that have to be calibrated. You can

use the CT01 to calibrate the following parameters on a VAVMax controller to suit your requirements:

• Zone temperature set point.

• Minimum Flow rate (L/s) – The minimum design air flow for that particular VAVMax controller.

• Maximum Flow rate (L/s) – The maximum design air flow for that particular VAVMax controller.

• K factor – The K factor is a value of calibration so the VAV Max can translate a pressure differential

at the VAV into an air volume passing through the VAV.

• Calibration of temperature sensor(s).

A-5 Commissioning

The Commissioning Mode on the CT01 is used for heater bank testing and driving the VAVMax

controller to a manual position for a time period of 4 hours. The Commissioning Mode can be

enabled by following the instructions below:

1. Log onto a VAVMax controller as per the instructions in the previous section.
2. Select Status and press the

Enter button. Now select Watches and press the Enter button.

3. Looking at the top of the LCD for menu names, use the navigation buttons to scroll left to the

Commissioning

menu.

The Commissioning menu contains the following information:

Item

Description

Commissioning Mode

Enable

Toggling this ON will enable the commissioning mode for 4hrs, after which

it will turn OFF. Toggling it ON again will turn commissioning mode OFF

again.

Commission mode for

4hrs

This is a count down timer that will indicate the time remaining before the

commissioning mode turns OFF.

Actuator Manual

Enable

This is to allow manual operation of the VAV actuator whilst

commissioning mode is ON.

Actuator Manual

Position

This is the required position when the Actuator Manual Enable is switched

ON.

Table A-1: 

Commissioning Menu