ROOM TEMPERATURE TRANSMITTERS

This unit is suitable for either drywall or junction box mounting. First, remove the cover of the housing and mount

the base of the Room unit to the wall, using the (2) 6/32” x 1” screws that are provided. Once the base is mounted to

the wall, make all of the proper connections and then place the cover back onto the unit. Now tighten the cover

down, using the (2) 1/16” Allen screws located in the bottom of the housing. The Room transmitter is provided with

a two pole terminal block for power and a two pole terminal block for the RTD, which allows for easy wiring of the

unit.

n

DUCT AND DUCT AVERAGING TEMPERATURE TRANSMITTERS

Duct Temperature Sensors - Drill a 3/8” hole in the duct and insert the probe through the hole until the foam pad is

tight to the duct. Now insert (2) screws through the mounting holes in the flange and tighten until the unit is

held firmly to the duct.

Duct Averaging Sensors - Drill a 3/8” hole in the duct and insert the averaging element through the hole until the

foam pad is tight to the duct. Now insert (2) screws through the mounting holes in the flange and tighten until the

unit is held firmly to the duct. The sensor should then be strung in a criss-cross pattern throughout the duct

(see Figure #2) using the mounting clips provided, in a pattern that covers the greatest surface area of the duct, to

insure that there is no stratification. When bending the copper tubing, be careful that you use a gradual bend and that

you DO Not kink the copper tubing.

n

FLUID IMMERSION TEMPERATURE TRANSMITTERS

The ACI Fluid Immersion type transmitters are provided with a 2.5", 4”, or 8” 304 series stainless steel thermowell. The

thermowell has a 1/2” external or process NPT threads and 1/2” internal or instrument NPT thread. All of the ACI

thermowells will accept a probe diameter of 0.250”.

n

STRAP-ON TEMPERATURE TRANSMITTERS

The ACI Strap-On transmitters are provided in a junction box with an adjustable 2” to 5” pipe clamp. The unit

should be mounted on the bottom side of the pipe to ensure good temperature transfer. In hot water applications

(over 150

o

F) it is recommended that the transmitter be remote located so as not to exceed the operating temperature

of the transmitter. Extra straps may be ordered for larger diameter pipes.

n

OUTSIDE AIR TEMPERATURE TRANSMITTERS

The ACI Outside Air transmitters are provided in two parts including a weatherproof enclosure and a 2” X 4”

junction box. The sensors will be mounted in the weatherproof enclosure and mounting hardware is provided. The

transmitter will be provided in the 1 gang junction box and should be mounted on an inside wall so as not to exceed

the operating temperature limits of the transmitter. This sensor should be mounted on either the North side of the

building or anywhere out of direct sunlight with the sensor probe pointed downward. Weatherproof Aluminum Bell

Boxes and NEMA 4X Polycarbonate enclosures are available upon request.

n

STAINLESS PLATE TEMPERATURE TRANSMITTERS

The ACI Stainless Plate temperature transmitters are mounted on the back of a 2” x 4” stainless plate. The sensor is

covered with a 1/8” foam insulation, which allows the sensor to sense the actual room temperature and ignore any

heat produced by the transmitter or drafts from within the wall. All mounting screws are provided.

12’ or 24’ Averaging Element

= Mounting Clips