TROUBLESHOOTING

No reading

No power to board - check voltage at power terminal - should be between +8 and 35 VDC

Reading too low

RTD wires shorted - check with ohmmeter - should be close to either 100 or 1000 Ohms

Improper range of transmitter (too low) - check current - should be between 4 and 20mA

Reading too high

RTD opened - check with ohmmeter - should be close to either 100 or 1000 Ohms

Improper range of transmitter (too high) - check current - should be between 4 and 20mA

RF Interference

Input power must be clean. Use twisted wires or shielded cable. RF resistant power supply

Use a shielded cable to connect the sensor -- connect the shield to ground

Encase the board in a RF shielded enclosure

Ohm

Meter

OHMS

Disconnect RTD before

testing sensor resistance

VOLTS

Measure across the - of the

temp transmitter and common

Red

Lead

Black

Lead

Volt

Meter

Black

Lead

Red

Lead

+ -

+1 to 5 VDC / +2 to 10 VDC

Output

CURRENT

Disconnect (-) and place

meter in Series

~ 100 Ohm or

~ 1000 Ohm

Current

Meter

Power

Supply

To Controller

Input or Power

Supply Common

+4 to 20 mA

Output

Black

Lead

Red

Lead

RTD

Power Supply /

Controller Common

Advertising