Before you begin, print all the related instructions or ensure that you can view the PDF version on another
computer for reference.

Notes:

• If you remove the TR 700 Battery, you will lose the backup power for the ThinkServer RAID 700 Adapter.

• Use any documentation that comes with the TR 700 Battery and follow those instructions in addition to

the instructions in this topic.

To remove the TR 700 Battery, do the following:

1. Remove all media from the drives and turn off all attached devices and the server. Then, disconnect all

power cords from electrical outlets and disconnect all cables that are connected to the server.

2. If the server is installed in a rack cabinet, remove the server from the rack cabinet and place it on a flat,

clean, and static-protective surface. See the Rack Installation Instructions that comes with the server.

3. Remove the server cover. See “Removing the server cover” on page 75.

4. Remove the cooling shroud. See “Removing and reinstalling the cooling shroud” on page 79.

5. Locate the ThinkServer RAID 700 Adapter, which is installed in the PCI Express card slot on the riser

card assembly 2. Then, disconnect all cables from the ThinkServer RAID 700 Adapter.

6. Remove the riser card assembly 2. The procedure is similar to that of the riser card assembly 1. See

“Replacing the riser card assembly 1” on page 160.

7. Remove the ThinkServer RAID 700 Adapter from the riser card assembly 2. See “Installing or removing

the RAID card” on page 90.

8. Remove the three screws first. Then, hold the TR 700 Battery and lift it up from the ThinkServer RAID

700 Adapter.

Note: Center the screwdriver when you remove the screws to avoid possible damage to any parts.

Figure 57. Removing the TR 700 Battery

9. Reinstall the ThinkServer RAID 700 Adapter to the riser card assembly 2. See “Installing or removing

the RAID card” on page 90.

10. Reconnect cables to the ThinkServer RAID 700 Adapter. See “Connecting the cables” on page 36.

11. Reinstall the riser card assembly 2. The procedure is similar to that of the riser card assembly 1. See

“Replacing the riser card assembly 1” on page 160.

What to do next:

100

ThinkServer RD340 User Guide and Hardware Maintenance Manual