180 V ac for 750-watt redundant power supplies compliant with 80 PLUS Titanium

• Maximum: 264 V ac

• Input frequency range: 47 to 63 Hz

Environment

Depending on the hardware configuration, some server models comply with ASHRAE class A4 specifications.
The other server models comply with ASHRAE class A3 specifications.

• For server models that meet all of the following configuration requirements at the same time:

These server models comply with ASHRAE class A4 specifications, such as air temperature, altitude,
and humidity as listed.

Hardware configuration requirements:

– Easy-swap-drive bays or eight 2.5-inch-drive

bays

– CPU: Lenovo-qualified; a maximum of 120-W

thermal design power; not low-power type (no
L-suffix in the CPU name)

– Do not have internal tape drives installed

– Two power supplies installed for redundancy

– PCIe card: Lenovo-qualified; power

consumption of each card does not exceed 15
W

Environment information:

– Dry-bulb temperature:

Operating: From 5°C (41°F) to 45°C (113°F)

Storage: From -40°C (-40°F) to 60°C (140°F)
in original shipping package

– Altitude: From 0 m (0 ft) to 3048 m (10 000 ft)

– Humidity:

Operating: From 8% to 90%
(non-condensing)

Storage: From 8% to 90% (non-condensing)

Note: When the altitude exceeds 900 m (2953 ft), the defined maximum dry-bulb temperature for
operation becomes a dependent variable. This temperature value decreases by 1 °C (33.8 °F) with
every 125 m (410 ft) of altitude increase.

• For the other server models:

These server models comply with ASHRAE class A3 specifications, such as the air temperature, altitude,
and humidity information as listed.

– Dry-bulb temperature:

Operating: From 5°C (41°F) to 40°C (104°F)

Storage: From -40°C (-40°F) to 60°C (140°F) in original shipping package

– Altitude: From 0 m (0 ft) to 3048 m (10 000 ft)

– Humidity:

Operating: From 8% to 85% (non-condensing)

Storage: From 8% to 90% (non-condensing)

Note: When the altitude exceeds 900 m (2953 ft), the defined maximum dry-bulb temperature for
operation becomes a dependent variable. This temperature value decreases by 1 °C (33.8 °F) with
every 175 m (574 ft) of altitude increase.