AUTOMATIC DRAIN VALVES (ADVs)

8DM Series purifiers are equipped with two electronic

automatic drain valves (ADVs) that automatically dis-

charge condensate from the coalescing filter. Drain

valve controls for one drain are on the front panel.

Controls for the second ADV are on the drain valve.

ADV operation is controlled by an electronic timer.

The front panel ADV controls allow the period of

drain opening (labeled DWELL SEC.) to be set from

0.5 sec to 10 sec and the drain cycle (labeled INTER-

VAL MIN.) to be set from 0.5 min to 60 min. The con-

trols for the second ADV allow the period of drain

opening to be set from 0.5 sec to 10 sec and the drain

cycle to be set from 0.5 min to 45 min.

Each ADV has a test button to help check ADV opera-

tion. When the button is pushed, the drain port will

click open with a clearly audible sound.

ADV Adjustment

To minimize air losses, the ADV timer should be ad-

justed to open the drain port just long enough to dis-

charge accumulated condensate. The timer is properly

set if only air discharges at the end of the open period.

If air discharges for longer than one second, set the

timer for a longer cycle or a shorter opening. If liquid

is discharging while the port is closing, set the timer

for a shorter cycle or a longer opening.

OPERATION

Airflow

8DM Series purifiers are rated at 100°F ambient air

temperature, 100°F inlet air temperature, 100 psig inlet

air pressure and 100% inlet relative humidity. Purifier

capacity at these conditions is as follows:

Model

Capacity (scfm)

8DM25

25

8DM50

50

8DM75

75

8DM100

100

8DM150

150

WARNING

High airflow, high inlet air temperature or low

inlet air pressure may cause poor purifier

performance,illness, injury or death. If the

purifier is operated at conditions different

from the rating conditions, adjust the inlet air

flow.

To determine adjusted inlet air flow, use the following

formula and the correction factors in Table VII.

Maximum Flow = Flow at Rating Conditions

x

F

p

x

F

t

x

F

a

Table VII

Purifier Sizing Correction Factors

Inlet Air

Pressure

Inlet Air

Temperature

Ambient Air

Temperature

psig

Factor

F

p

°F

Factor

F

t

°F

Factor

F

a

50

0.56

80-100 1.00

100

1.00

60

0.65

110

0.74

105

0.97

70

0.74

120

0.56

110

0.94

80

0.83

115

0.91

90

0.91

120

0.88

100

1.00

110

1.02

125

1.06

150

1.11

Start-Up

Once installation is completed as directed and proper

airflow is determined, the purifier is ready for start-up.

WARNING

Compressed air and compressed air equip-

ment can be dangerous unless safety pre-

cautions are observed. Anyone who works

with this equipment must read and carefully

follow these instructions.

Models 8DM75, 8DM100 and 8DM150 include a

crankcase heater in the refrigeration circuit. The first

three steps of this start-up procedure apply only to

these models.

1. Turn the front-panel power switch OFF.

2. Supply power to the purifier and let the crankcase

heater warm up for four hours.

Pyramid 8000

®

Series Purifiers (Bulletin 289)

9