MCM ♦ ProLinx Gateway

Serial Port Modbus Error and Status Data

Modbus Master/Slave

Driver Manual


Page 40 of 80

ProSoft Technology, Inc.

October 16, 2009

4.3.4 Modbus Configuration Error Word

Modbus Configuration Error Word values are stored in protocol-specific registers.
The following table lists the register address used for each port that may exist on
the gateway.

Modbus Port

Configuration Error Word Register

0 4407

1 4807

2 5207

3 5607

If any of these registers contains a non-zero value, it indicates a problem with the
configuration of the associated port. The following table lists the codes, a
description of the problem, and which parameters to change tocorrect the error
condition within the configuration file.

Bit Code

Description

0

0x0001

Invalid Enabled parameter (Yes or No)

1

0x0002

Invalid RS-Interface parameter (0 to 2)

2

0x0004

Invalid Type (Master or Slave)

3

0x0008

Invalid Protocol (RTU or ASCII)

4

0x0010

Invalid Baud Rate

5

0x0020

Invalid Parity (None, Odd, Even)

6

0x0040

Invalid Data Bits (7 or 8 bits)

7

0x0080

Invalid Stop Bits (1 or 2)

8

0x0100

Invalid Use CTS Line (Yes or No)

9

0x0200

Retry Count Invalid (0 to 10)

10

0x0400

Invalid Floating Point Data:

Float Flag not Yes or No

Float Start less than 0 or

Float Offset is Invalid

11

0x0800

Invalid Internal Slave ID (1 to 255) (Slave Only)

12

0x1000

Invalid Entry for Register Offset Data (Slave Only)

13 0x2000

Reserved

14 0x4000

Reserved

15 0x8000

Reserved