7.2.4 Baud

Rate

This is the baud rate to be used on the slave port. It must match the baud rate
setting used by the remote Master serial network that will be connected to this
slave port. Each port/network can use different baud rates, if required. It is not
necessary to have all the ports on the gateway set to the same baud rate.

To maximize the port multiplexing capability of the gateway, it is recommended, if
possible, that you set the baud rate on the Master port and on the attached slave
as high as the slave can accommodate, up to 38,400; then set the baud rate for
the gateway slave ports and remote Master networks to a lower setting. This will
help prevent multiple Masters from overloading the response capability of the
single slave and the gateway.

Enter the baud rate as a value, shown in this list.

Baud Rate

Parameter Value

110

110

150

150

300

300

600

600

1200

12

OR

1200

2400

24

OR

2400

4800

48

OR

4800

9600

96

OR

9600

14,400

14,

114

OR

14400

19,200

19,

192

OR

19200

28,800

28,

288

OR

28800

38,400

38,

384

OR

38400

57,600

57

OR

576

115,200

115

OR

1152

Note: On all ProLinx gateways, data from the application port on the main board, serial Port 0, is
not buffered. Packets go directly to and from the serial chipset to the processor. This has the

potential to cause the serial communications to become erratic at baud rates above 38,400 baud.
ProLinx gateways with 4 serial ports have a separate serial interface board for serial Ports 1, 2,
and 3. These serial ports are buffered, and can handle communications up to 115,200 baud.

7.2.5 Parity

N

ONE

,

O

DD

,

E

VEN

Parity is a simple error checking algorithm used in serial communication. This
parameter specifies the type of parity checking to use.

All devices communicating through this port must use the same parity setting.