Table 14. Oil Safety Switch

Pressure

Carlyle

Danfoss

Time Diff. Psi (bar)

Part No.

Part No.

Delay

Cut-In

Cut-Out

Reset

634-2008

OR

60B2101

P529-2130

45 sec.

8 – 11

4 - 8

Manual

634-2050

(.55 - .76)

(.28 - .55)

OR

60B2151

P529-2100

Pressure

Carlyle

Johnson

Time Diff. Psi (bar)

Part No.

Part No.

Delay

Cut-In

Cut-Out

Reset

O6DA660115

P345

45 sec.

8 – 11

4 - 8

Manual

(.55 - .76)

(.28 - .55)

Table 15. Part Load Performance Multipliers

Multiplication Factor

Multiplication Factor

Compressor Model

For 1 Bank Unloaded

For 2 Bank Unloaded

Capacity

Power

EER

Capacity

Power

EER

All 4 Cylinder Models

.49

.57

.86

-

-

-

All 6 Cylinder Models

.67

.73

.92

.32

.46

.70

Table 16. Required Differential Pressure
for Unloader Operation

Suction Pressure

P Required-Discharge Minus

Application Range PSI (Bar)

Suction Pressure PSI (Bar)

O6D

O6E

L.T. R-502, 404A, 507

10-25

(1.7-2.7)

30

(2.1)

30

(2.1)

M.T. R-502, 404A, 507

30-60

(3.1-5.2)

40

(2.8)

45

(3.1)

L.T. R-12, 134a

10-30

(1.7-3.1)

30

(2.1)

35

(2.4)

M.T. R-22 or H.T. R-22

30-90

(3.1-7.2)

50

(3.5)

55

(3.8)

Multiply compressor rating data by above factors when used with blocked suction unloading.

3-Phase Voltage Monitor

The microprocessor-based voltage and phase sensing circuit
constantly monitors the three phase voltages to detect
harmful power line conditions. When a harmful condition is
detected, the phase monitor output relay is deactivated after
a specified trip delay. The output relay reactivates after
power line conditions return to an acceptable level for a
specified amount of time (Restart Delay). The trip delay
prevents nuisance tripping due to rapidly fluctuating power
line conditions.

The Bicolor LED indicator light is green in normal conditions
and red during trip conditions. On initial start-up, if the light is
continuously red, the unit electrical phase may need to be

reversed. Each main power line should be checked for
proper voltage and imbalance prior to reversing a phase.
Also check the settings of the Voltage Monitor for proper field
conditions.

For semi-hermetic compressor units, two of the three power
monitor leads on the Voltage Monitor to L1, L2, and L3 may
need to be switched. For units with Scroll or Screw
compressors, which are rotation sensitive, two of the main
power lines to the compressor unit will have to be switched to
match the correct rotation of the compressors. The rotation
of Screw and Scroll compressors has been properly phased
in the manufacturing plant prior to shipping.