11 commissioning, Commissioning – Grant Products HPAW155 User Manual

Page 38

Advertising
background image

34

Commissioning

ATC

Parameter

Description

Range

Set Value

Comments

0

Return water temperature to start electrical heater

0˚C

– 30˚C

˚C

Do not Adjust

1

Desired Return water temperature setting

10˚C

– 60˚C

˚C

SET TO 60˚C

2

Defrost cycle

30 Min

– 90Min

Min

Do not Adjust

3

Coil temperature point to start defrosting

-30˚C

– 0˚C

˚C

Do not Adjust

4

Coil temperature point to stop defrosting

2˚C

– 30˚C

˚C

Do not Adjust

5

Max time for defrosting

1 Min

– 12Min

Min

Do not Adjust

7

Restart after power failure

0/1

1

Do not Adjust

0=NO, 1=Yes

9

Water pump working mode

0/1

1

Do not Adjust

0 = Cont, 1 = Normal

Fan motor working mode

A

0 = daytime working mode

0/1

1

Adjustable

1 = night time working mode

B

Target superheat

-F

– F

3

Do not Adjust

C

Manual control paces of EEV

0

– 50

35

Do not Adjust

BTC

Item

Access

Active

Mode

Set Value

Range

OUTDR Start

1

Always

all

˚C

1 to 29˚C

OUTDR DSGN

1

Always

All

˚C

-50 to 0˚C

BOIL START

1

Always

All

˚C

1 to 65˚C

BOIL DSGN

1

Always

All

˚C

21 to 104˚C

BOIL MAX

0

Always

All

˚C

48 to 107˚C, OFF

BOIL MIN

0

Always

All

˚C

OFF, 26 to 82˚C

DIFF

0

Always

All

AU

AU, 1 to 23˚C

DHW BOIL TARGET

0

Always

All

˚C

OFF, 21 to 104˚C

‘pump’ DLY

0

Always

All

secs

OFF, 20 secs to 9:55 mins

WWSD

1

Always

All

˚C

1 to 38

˚C

, OFF

(Warm Weather Shut Down)

11 Commissioning

Please complete the following settings:

11.4 Record of ATC and BTC Settings