Fault Finding

39

Protection/failure

Display

Inlet water temperature sensor failure

PP 1

Coil temperature sensor failure

PP 3

Ambient temperature sensor failure

PP 5

Winter anti-freeze protection

PP 7

High pressure

EE 1

Low pressure

EE 2

Flow switch

EE 3

Wrong/ miss phase

EE 4

Electrical shock protection

EE 5

Defrosting

Defrosting indicator

communication failure

EE 8

Item Field

Num Field

Display

E01

Err

EEprom read error

BOIL OUT

SHr

HP Flow sensor short

BOIL OUT

OPn

HP Flow sensor open

BOIL IN

SHr

HP return sensor short

BOIL IN

OPn

HP return sensor open

SUP

SHr

Supply sensor short

SUP

OPn

EE 3Supply sensor open

OUTDR

SHr

Outdoor sensor short

OUTDR

OPn

Outdoor supply sensor open

Figure 13-4: ATC fault codes

Figure 13-3: BTC sensor resistance table

Figure 13-5: BTC fault codes

Temperature

Resistance

Temperature

Resistance

Temperature

Resistance

Temperature

Resistance

˚C

k

W

˚C

k

W

˚C

k

W

˚C

W

-46

490.813

-7

46.218

32

7.334

71

1,689

-43

405.710

-4

39.913

35

6.532

74

1,538

-40

336.606

-1

34.558

38

5.828

77

1,403

-37

280.279

2

29.996

41

5.210

79

1,281

-34

234.196

4

26.099

43

4.665

82

1,172

-32

196.358

7

22.763

46

4.184

85

1,073

-29

165.180

10

19.900

49

3.760

88

983

-26

139.402

13

17.436

52

3.383

91

903

-23

118.018

16

15.311

54

3.050

93

829

-21

100.221

18

13.474

57

2.754

96

763

-18

85.362

21

11.883

60

2.490

99

703

-15

72.918

24

10.501

63

2.255

102

648

-12

62.465

27

9.299

66

2.045

104

598

-9

53.658

29

8.250

68

1.857

107

553

BTC