AACC 2000 Carbon Nov. 1, 1997

90










Select Low-point Calibration

This is the Calibration Status display. This display shows
that no input is selected for calibration.

nonE:

No selection

ip1.L:

Input 1 (PV1) calibration low-point

selected

ip1.H:

Input 1 (PV1) calibration high-point

selected

ip2.L:

Input 2 (PV2) calibration low-point

selected

ip2.H:

Input 2 (PV2) calibration high-point

selected

Use

/

to select the parameter for the Low Calibration

point of Input 1, ‘

ip1.L’.

Press

Adjust low-point calibration

This is the display for adjusting the Low Calibration point of
Input 1. The lower readout is a live reading of the process
value, which changes as the input changes.
Make sure that the calibration source is connected to the
terminals of Input 1, switched on and feeding a signal to the
controller. It should be set to the desired low-point
calibration value. If the lower readout does not show this
value, then use

/

to adjust the reading to the required

value.

Press

to return to the ‘

ip-List’ header.

To perform the High-point Calibration, repeat the above
procedure, selecting ‘

ip1.H’ in the ‘CAL.S’ display for

adjustment.

Press

three times.

Calibration type

USEr’ was selected for the Low-point Calibration, and has

remained selected.

Press