3. Operation

3.5 Upsilon STS customization

The monitoring parameters must
be identical for the two sources.
These parameters depend on the
tolerances of the connected loads.

Return to preferred source after transfer

Nominal source voltage

Overvoltage threshold

Undervoltage threshold

Nominal source frequency

Frequency tolerances

Phase error tolerance between the two sources

Factory setting

Automatic

400 V

Un +10%

Un -10%

50 Hz

±

5%

±

15

°

Customization

Manual / Automatic

380 / 400 / 415 V

Un +5% to Un +20%
in 1% steps

Un -5% to Un -20%
in 1% steps

50 / 60 Hz

+1% to +10%
-1% to -10%
in 0.5% steps

±

1

°

to

±

45

°

in 1

°

steps

1 - Press the menu button 26 .

2 - Select "Setup", then "Customization" using the function buttons 23 marked or .

3 - Confirm the order by pressing the function button 23 marked

.

4 - Enter the password.

The password

Ш

Ш

Ш

is set in the factory.

Select "Setup", then "Password" to personalise the password.

PERSONALIZATION

E
S
C

Current settings

400 V
10%
10%
50 Hz
5%
5%
15

°

YES

Nominal voltage

Overvoltage threshold

Undervoltage threshold
Nominal frequency
Overfrequency threshold
Underfrequency threshold
Phase sync tolerance
Retransfer