4. Maintenance

4.1 Identification of anomalies

4.2 Transfer to the manual bypass

Transfer to the manual bypass for source
S1:

1 - Manually transfer the load to source S1.

2 - Set switch Q2 4 to the OFF position
(position 0).

3 - Set switch Q1BP 6 to the ON position
(position 1).

The load is supplied by source S1 via the
bypass.

4 - Set switches Q1 1 and Q3 7 to the
OFF position (position 0).

The operation for source S2 is
identical, using switches Q2 and
Q2BP.

Interlocking of the bypass lines is
ensured by use of a single key that
must be inserted on the bypass
switch to be operated.

General-alarm

LED 21

-

-

-

-

-

S1 31 or S2 32

LED

-

-

-

-

Static-switch

LED 33 or 34

-

-

-

-

-

The meaning of all these anomalies are detailed on the display:
Select the alarm: the corresponding informations are displayed.

Buzzer

Beeps

Beeps

Beeps

Beeps

-

-

Meaning

Internal STS fault.

Source outside
tolerances, load still
supplied.

Source outside
tolerances, no voltage.
The load cannot be
supplied by this source.

Static-switch fault.

Overload.

Load not supplied.

System output

LED 38

-

-

-

-

Q1

Q5 Q6

Q2

Q1BP

Q2BP

Q3

0

1

0

1

0

0

0

1

1

1

Q1

Q5 Q6

Q2

Q1BP

Q2BP

Q3

0

1

0

1

0

0

0

1

1

1

Q1

Q5 Q6

Q2

Q1BP

Q2BP

Q3

0

1

0

1

0

0

0

1

1

1

1

4

6

7