Lonworks interface product manual (sha-ln16uab), Details of lonworks network variables – Sanyo CHX06052 User Manual
Page 150

2-132
Remote Control Functions
7. LonWorks Interface product Manual (SHA-LN16UAB)
7. Details of LonWorks Network Variables
[nv1] Unit start/stop command
network input SNVT_switch nviOnOff_0 0;
network input SNVT_switch nviOnOff_0 1;
network input SNVT_switch nviOnOff_0 2;
network input SNVT_switch nviOnOff_0 3;
These input n etwork v ariables ar e used to ch ange the start/stop
status of the ind oor unit.
If star t/stop is only done from an A/ C unit side (as with the rem o te
controll er), th en it is not n e c e ssary to use th ese n e twork vari ables .
Contents
state 0: Stop
value (Not used)
1: start
[nv2] Unit start/stop status notification
network output SNVT_sw itch nvoOnOff_0 0 ;
network output SNVT_sw itch nvoOnOff_0 1 ;
network output SNVT_sw itch nvoOnOff_0 2 ;
network output SNVT_sw itch nvoOnOff_0 3 ;
These output n e twork v a riab les ar e us ed to pro v ide notification of
the un it’s cur r en t s t ar t/s top s t atus and the therm o s t at ON/OF F s t atus .
The y are als o o u tput when th e s t atus h a s be en ch anged from an A / C
unit side (as wit h the rem o te con t roller) .
They are outp ut when the Lo nWorks Interface or the A/C u nit
power is r e set.
When the ind oor units ar e su bject to group control, “thermostat
ON” is output when 1 or more indoor unit is thermostats ON, and
“thermostat OFF” is ou tput w hen all indoor unit are thermo stats
OFF.
Contents
state 0: Stop value 0: T hermostat OF F
1: Start
200: T hermostat ON
[nv3] Te mperature setting command
network input SNVT_temp _p nviS etpoin t _0 0;
network input SNVT_temp _p nviS etpoin t _0 1;
network input SNVT_temp _p nviS etpoin t _0 2;
network input SNVT_temp _p nviS etpoin t _0 3;
These inpu t n e twork variables ar e used to change the indoor unit
tem p eratur e s e tti ng.
If th e tem p era t ure se tting is onl y ch anged from an A/C uni t sid e (as
with the r e m o te control l er) , the n it is not n e c e ssar y to use th ese
network var iables.
When a temper ature above th e u pper limit of the temper ature wh ich
can be set b y the indoor units has been specified, it will be set to the
upper limit; con versely, when a temperatur e b elow the low er limit
has been spec ifi e d, it will be set to th e lower l i m it.
Contents
Valid ra ng e
Auto heat/cool mode: 62 - 80°F (17 - 27°C)
Heat mo de:
60 - 78°F (16 - 26°C)
Cool mo de:
64 - 86°F (18 - 30°C)
Dr y mo d e :
64 - 86°F (18 - 30°C)
F an mode:
Temp. setting not used.
Temperature settings are made in units of 1.8°F (1.0°C). (Values
°
after the decimal point are discarded.)
* Be awa r e tha t t h e tem p eratur e setting r a nges m a y var y a ccord ing to
the models of th e outdoor and in door units.
[nv4] T emperature setting status notification
network output SNVT_temp_p nvoSetpo int_01;
network output SNVT_temp_p nvoSetpo int_01;
network output SNVT_temp_p nvoSetpo int_02;
network output SNVT_temp_p nvoSetpo int_03;
These output network v ariables ar e output w h en the temperature
setting status is changed.
The y are als o o u tput when th e s t atus h a s be en ch anged from an A / C
unit side (with th e rem o te con t rol l er).
They are outp ut when the Lo nWorks Interface or the A/C u nit
power is r e set.
Contents
Valid ra ng e
Output range:
60-86°F (16-30°C)
T e m p . u n i t :
1.8°F (1.0°C)
* Be awa r e tha t t h e tem p eratur e setting r a nges m a y var y a ccord ing to
the models of th e outdoor and in door units.
[nv5] Operating mode setting command
network input SNVT_hva c _mode nviHea tC ool_00;
network input SNVT_hva c _mode nviHea tC ool_01;
network input SNVT_hva c _mode nviHea tC ool_02;
network input SNVT_hva c _mode nviHea tC ool_03;
These input n etwork v ariables ar e used to change the indoor u nit
operating mode.
If the op erating mode setting is on ly changed from an A/C unit
side (as with th e rem o te control l er), then it is n o t nec e ssar y to use
thes e n e twork v a riables .
Contents
0: Auto heat/cool
5: Dry
1: Heat
9: F a n
3: Cool
* Th e operating modes that can be set may va ry ac c o rding t o the
models of the ou tdoor and indoor units.
* Settings other than th e above ar e ignor ed.
[nv6] Operating mode status notification
network output SNVT_hvac_mode nvoH eatCool_00;
network output SNVT_hvac_mode nvoH eatCool_01;
network output SNVT_hvac_mode nvoH eatCool_02;
network output SNVT_hvac_mode nvoH eatCool_03;
These output n e twork v a riab les ar e ou tput wh en the operating m ode
has been ch anged.
The y are als o o u tput when th e s t atus h a s be en ch anged from an A / C
unit side (with th e rem o te con t rol l er).
They are outp ut when the Lo nWorks Interface or the A/C u nit
power is r e set.
Contents
0: Auto heat/cool 5: Dr y
1: Heat
9: F a n
3: Cool
[nv7] Option 1 setting command
[nv9] Option 2 setting command
network input SNVT_switch nviOption1_0 0;
network input SNVT_switch nviOption1_0 1;
network input SNVT_switch nviOption1_0 2;
network input SNVT_switch nviOption1_0 3;
network input SNVT_switch nviOption2_0 0;
network input SNVT_switch nviOption2_0 1;
network input SNVT_switch nviOption2_0 2;
network input SNVT_switch nviOption2_0 3;
These inpu t n e twork variables are used to make th e indoor unit
option settings.
Two of the following 4 option settings can be selected:
remote-contro ller prohibit, fan speed setting, air di rection setting,
and filter sign r e set.
Make ch anges using the DIP switc hes on the main circuit bo ard.
When option s ettings are not made from the LonWorks, it is not
neces s a r y to us e thes e n e twork v a riables .
[nv8] Option 1 setting status notification
[nv10] Option 2 setting status notification
network output SNVT_sw itch nvoOption1 _00;
network output SNVT_sw itch nvoOption1 _01;
network output SNVT_sw itch nvoOption1 _02;
network output SNVT_sw itch nvoOption1 _03;
network output SNVT_sw itch nvoOption2 _00;
network output SNVT_sw itch nvoOption2 _01;
network output SNVT_sw itch nvoOption2 _02;
network output SNVT_sw itch nvoOption2 _03;
These ou tput n e twork var i ables provide notif ication of ch anges in
the st atus of the indoor unit opt io n settings .
Two of the following 4 optio n s e t tin gs can be s e lect ed:
remote-contro ller prohibit, fan speed setting, air di rection setting,
and filter sign r e set.
Make ch anges using the DIP switc hes on the main circuit bo ard.
They are ou tput when th e LonW orks Interface or A/C unit pow er is
reset.
Temp.
setti ng
Operat i n
g mode
O
O
value
(No t us ed )
100
120
140
150
160
180
200
Fan speed
s e ttin g
Auto
Hi gh
Mediu m
Lo w
Sw in g
F1
F2
F3
F4
F5
Filter
sign
F ilter sign is reset w h e n
data is up date d .
F1
F2
F3
F4
F5
*
Positions F 4
and F5 can no t be
set for cool- a n d
dry-mode
operation .
state
0
1
Othe r
120
200
150
100
(Not
us ed )
Othe r
200
170
140
110
(Not
us ed )
Othe r
Sw in g
80
50
Operat i ng
mode
O
value
0
100
120
140
150
160
180
200
Remote-
controller
proh i b i t
Auto
Hi gh
Mediu m
Lo w
Sw in g
F1
F2
F3
F4
F5
state
0
1
120
200
150
100
1
50
200
170
140
110
1
0
Sto p
80
50
0
0
1
OFF
ON
Sto p
Ve r y
0
Remote-
controller
proh i b i t
Start/stop
ope rati on
O
O
O
O
O
Air
di rect i on
s e ttin g
Temp.
s e ttin g
Start/stop
ope rati on
O
O
O
O
Fan speed
s e ttin g
Air
di rect i on
s e ttin g
Filter
sign
O :Permitted
:
Prohibite d
O :Permitted
O
O
:Prohibited