12. SERVICE PROCEDURES
9)
Outdoor Fan does not Run for CL4232.
10) Compressor does not Run.
• Check fuse on PCB Ass’y in
outdoor unit for continuity.
• Check resistance of primary
winding of transformer. (TR)
1038_X_S
If fuse blows,
• Check PTC.
• Check compressor motor capacitor
(RC1).
Wait for 30 minutes until com-
pressor has cooled.
Compressor runs.
Compressor internal thermal
protector is operated.
• Check power supply voltage.
Is voltage abnormally low?
NO
• Is outdoor heat exchanger coil dirty
or are there obstacles near air
suction inlet?
• Check resistance of compressor
motor winding.
1039_X_S
OK
OK
Advertising
This manual is related to the following products:
See also other documents in the category Sanyo Conditioners:
- ECO-i WCHDZ20053
- CL0951
- ECO G SPW-GU075XH
- CM1972
- CR365GX56
- 42XS32A
- CL2432A
- 9
- KH3072R / C3072R
- CH0971
- 26UW72R
- C2432
- CR1304GDZH8
- KH2672R
- ECOi C0905DXHN8
- CH1251
- 30KS32A
- Concealed Duct & Heat Pump H 13.9-14.9 SEER
- 42TLS32A
- CL2462R
- C1251
- DHX3652
- 42XHW72R
- 09KS71
- C3632A
- 18KS72
- 12XS71
- ECO R410A
- KS2472
- INVERTER SPLIT SYSTEM 8.53E+13
- C3082
- KHHS2672R
- CHX06052
- CL1211
- CH3082
- Indoor Unit thx1852
- 42TW72R
- KHS1872
- CHDZ14053
- CL0971
- CHDX14053
- 09KS51
- 12RLS11
- CL1852
- 26XW72R
- KHS2672R
- KHS1251
- C1271
- CHX06052
- 42TS32A
- 12KHS71
- CXS2432
- C1852
- 12KS71
- CH0922
- 18XS72
- CH1872
- 18XLS72
- CL1251
- CH2432
- CH0951
- 12KLS71
- DC Inverter Split System XHS1271
- Cool/Dry
- CH2472
- C4272R
- 18KLS72
- XS2432
- CH4272R H/P
- 36TS32A
- 36UW72R
- AHX0952
- KHS2432
- 26TW72R
- DC INVERTER SPLIT SYSTEM AIR CONDITIONER C1271
- CH3632
- 18XLS52
- R410A