SERVICE TECH. INFORMATION

SECTION 5

22

5A.

TROUBLESHOOTING

AUTOMATIC ELECTRONIC DIAGNOSTICS

The faceplate timer (PWA) computer has a self-diag-

nostic function for the electrical system, except for

input power and water meter.

The computer monitors the elec-

tronic components and circuits

for correct operation. If a mal-

function occurs, an error code

appears in the faceplate display.

The chart below shows the error codes that could

appear, and the possible defects for each code.

While an error code appears in the display, all face

plate buttons are inoperable except the SELECT

button. SELECT remains operational so the service

person can make the MANUAL INITIATED ELEC-

TRONIC DIAGNOSTICS (below) to further isolate

the defect, and check the water meter.

CODE

POSSIBLE DEFECT

MOST LIKELY

LESS LIKELY

Err1, Err3,

Err4

wiring harness or connection to switch / position switch / motor inoperative / valve defect causing

high torque

Err1, Err3,

Err4

wiring harness or connection to switch / position switch / motor inoperative / valve defect causing

high torque

Err4

high torque

See faceplate timer (PWA) replacement on page 23.

Err5

faceplate timer (PWA)

PROCEDURE FOR REMOVING ERROR CODE FROM FACEPLATE: 1. Unplug transformer 2. Correct defect

3. Plug in transformer 4. Wait for 6 minutes. The error code will return if the defect was not corrected.

MANUAL INITIATED ELECTRONICS DIAG-

NOSTICS

1.

To enter diagnostics¼

- - from a error code display, press the #1 SELECT

button.

- - from a time display, press and hold the #1

SELECT button for 3 seconds.

You will see 1 of the following displays. All of the

displays show what position the valve is in, if the

turbine is operating, and the position switch open or

closed status.

FLOW RATE

Serv

DAY

TIME REMAINING

FLOW RATE

Fill

TIME REMAINING

FLOW RATE

2.

Press the ON/OFF-HOLD button to advance the

valve to the next position. To verify component

operation, or to possibly isolate a defect, observe

the following.

POSITION SWITCH STATUS: WIth the valve in

service, or any of the recharge cycles, the switch

indicator will show open

. While the valve is

rotating from 1 position to another, the indicator will

show the switch closed

. A defect is probable if

indications vary from this pattern.

WATER METER TURBINE: With soft water in use,

the turbine flow rate display continually repeats a

000 to 140 count for each gallon of water passing

through the turbine. The display will remain a

steady¼ 000 if soft water is not in use (open a nearby

soft water faucet to check).

If you don’t get a reading in the display, with faucet

open, pull the sensor from the valve outlet port. Pass

a small magnet back and forth in front of the sensor.

You

8

7

6

5

4

3

2

1

SALT

LEVEL

SIGNAL

LEVEL