General product specifications – Rackmount Solutions XRT Series User Manual
Page 36
35
7. GENERAL PRODUCT SPECIFICATIONS
XRT600
(XRT600/2)
XRT1000
(XRT1000/2)
XRT1500
XRT2000
(XRT2000/2)
XRT2001
XRT2002
Acceptable input
volts
92-140v
(169-268v)
92-140v
(169-268v)
92-140v
N/A
92-140v
(169-268v)
176-278v
152v-267v
Output Voltage
(on-line) +/- 10%
120v
(230v)
120v
(230v)
120v
N/A
120v
(230v)
120v/240v
120/208v
Nominal input
frequency
60 Hz
(50 Hz)
60 Hz
(50 Hz)
60 Hz
N/A
60 Hz
50 Hz
60 Hz
60 Hz
Input protection
Reset-able circuit breaker
Frequency limits
(online)
60 Hz. +/- 3 Hz
(50 Hz. +/- 3 Hz. )
Transfer time
4 ms Typical
Max load
(VA/watts)
600 /600
1000 / 1000
1500 / 1500
2000 / 2000
2000 / 2000
2000 / 2000
On Battery
Output Voltage
120v
(230v)
120v
(230v)
120v (N/A)
120v (230v)
120v /
240v
120v /
208v
On Battery
frequency
60 Hz +/-0.1 Hz. Unless synchronized to utility during brownout.
(50 Hz +/- 0.1 Hz. Unless synchronized to utility during brownout)
On Battery
waveform
Low distortion sine wave
Protection
Over-current and short circuit protected: latching shutdown on overload
Surge energy
rating
480 joules: one time 10 to 1000
µ s waveform ( 120 VAC units )
Surge current
capability
6500A maximum: one time 8 to 20
µ s waveform (120 VAC units )
Surge response
time
0 Ns (instantaneous) normal mode, <5 Ns common mode
Surge volts let
thru
< .2%
Noise filter
Normal and common mode EMI /RFI suppression, 100 kHz to 10 MHz
Battery type
Spill proof, sealed, maintenance free, lead-acid
Typical battery
life
5 years
Typical recharge
time
4 hours for a single battery pack
Operating temp
0 to 40
°C (+32 to 104°F)
Operating &
storage relative
humidity
0 to 95% non-condensing
Storage
temperature
-15 to +45
°C (+5 to 113°F)
Operating
elevation
0 to 3000 meters ( 0 to 10,000 ft. )
Electromagnetic
immunity
IEC 801-2, 801-3, 801-4: Severity level 5
Audible noise
<45 dB @ 1 meter
Audible Alarm
On overload, On battery, Low battery warning, check fan
Communication
s port
DB-9 Minuteman standard