Commands and monitoring from the computer – Toshiba TOSVERT VF-S11 User Manual

Page 46

Advertising
background image

E6581222

44

8. Commands and monitoring from the computer

Across the network, instructions (commands and frequency) can be sent to each inverter and the
operating status of each inverter can be monitored.

8.1. Communication commands (commands from the computer)

■ Communication command (Communication number: FA00)

Commands can be executed on inverter frequencies and operation stop through communications.
The VF-S11 series can enable command and frequency settings through communications irrespec-
tive of settings of the command mode () and frequency mode (). However, if “48:
Forced change from communication to local,” “52: Forced operation,” or “53: Fire speed” is set by in-
put terminal function selection ( to ), a change to a command other than communica-
tion and to a frequency command is feasible through a contact on the terminal board.
Once the communication command (FA00) is set to enable communication command priority and
frequency priority, both priorities will be enabled unless OFF is set, power is turned off or is reset, or
standard shipment setting () is selected. Emergency stop, RY terminal output hold and OUT
terminal output hold are always enabled even though communication command priority is not set.

Table 1 Data construction of communication commands (communication number: FA00)

bit Specifications

0

1

S7 S9/nC1/S11

Remarks

0 Preset speed operation

frequencies 1

9

1 Preset speed operation

frequencies 2

2 Preset speed operation

frequencies 3

3 Preset speed operation

frequencies 4

Preset speed operation is disabled or
preset speed operation frequencies (1-
15) are set by specifying bits for preset
speed operation frequencies 1-4.

(0000: Preset speed operation OFF,

001-1111: Setting of preset speed
operation frequencies (1-15))

9

Preset speed operation can be
disabled or a preset speed op-
eration frequencies (1-15) can
be specified by combining 4 bits
variously.

4 Motor selection (1 or 2)

(THR 2 selection)

Motor 1

(THR 1)

Motor2

(THR2)

-

9

THR1 : PT=set value, vL, vb, tHr
THR2 : PT=0, F170, F172, F173

5 PI control

Normal operation

PI OFF

-

9

6 Acceleration/deceleration

pattern selection (1 or 2)
(AD2 selection)

Accelera-

tion/deceleration

pattern 1 (AD1)

Accelera-

tion/deceleration

pattern 2 (AD2)

9

9

AD1 : ACC, DEC,
AD2 : F500, F501

7 DC braking

OFF

Forced DC braking

9

9

8 Jog run

OFF

Jog run

9

9

9 Forward/reverse run

selection

Forward run

Reverse run

9

9

10 Run/stop

Stop

Run

9

9

11 Coast stop command

Standby

Coast stop

9

9

12 Emergency stop

OFF

Emergency stop

9

9

“E” trip

13 Fault reset

OFF

Reset

9

9

No data is returned from the
inverter.

14 Frequency priority selec-

tion

OFF

Enabled

9

9

Enabled regardless of the set-
ting of 

15 Command priority selec-

tion

OFF

Enabled

9

9

Enabled regardless of the set-
ting of 

Note: For the reset command, no data will be returned.
Ex.: Forward run: (PFA008400) CR

1 is specified for bit 15 (communication command: enabled) and bit 10 (operation command).

BIT15

BIT0

1

0

0 0

0

1 0

0

0 0

0

0 0

0

0 0

Ex.: Reverse run: (PFA008600) CR, (PFA00C600) CR

8600H : To disable frequency instructions from the computer
C600H : To enable also frequency instructions from the computer

FA00:

0

0

4

8

Advertising