Input terminal board status (fd06, fe06), Output terminal board status (fd07, fe07) – Toshiba TOSVERT VF-S11 User Manual

Page 56

Advertising
background image

E6581222

54

„

Input terminal board status (FD06, FE06)

Input terminal board status (status immediately before the occurrence of a trip):

Communication Number FE06

Input terminal board status (current status):

Communication Number FD06

In case “0: No assignment function” is selected in function selection, inverter operations will not be
affected even when terminals are turned on and off. Therefore, the terminals can be used as input
terminals for customer’s own use.

The input terminal function selection parameter is used to select a function for each input terminal.
When monitoring the operating status, check what function is assigned to each internal terminal.

Data construction of input terminal board (FE06)

Bit

Terminal name (extended)

Function (parameter title)

0

1

0

F

Input terminal selection 1 (f111)

OFF

ON

1

R

Input terminal selection 2 (f112)

OFF

ON

2

RES

Input terminal selection 3 (f113)

OFF

ON

3

S1

Input terminal selection 4 (f114)

OFF

ON

4

S2

Input terminal selection 5 (f115)

OFF

ON

5

S3

Input terminal selection 6 (f116)

OFF

ON

6

VIB *1

Input terminal selection 7 (f117)

OFF

ON

7

VIA *1

Input terminal selection 8 (f118)

OFF

ON

8 ~ 15

-

-

-

-

*

1: It is valid only when it is selected as contact input by .

It is effective only when it is chosen with F109 for input of a contact point.
Ex.: FE06 data when the F and S1 terminals are ON: 0009H

BIT15

BIT0

0

0 0

0

0 0

0

0 0

0

0 0

1

0 0

1

„

Output terminal board status (FD07, FE07)

Output terminal board status (status immediately before the occurrence of a trip):

Communication Number FE07

Output terminal board status (current status):

Communication Number FD07

The output terminal function selection parameter is used to select a function for each output terminal.
When monitoring the operating status, check what function is assigned to each output terminal.

Data construction of output terminal board (FD07,FE07)

Bit

Terminal name

Function (parameter title)

0

1

0

RY

Output terminal selection1(f130)

OFF

ON

1

OUT

Output terminal selection1(f131)

OFF

ON

2

FL

Output terminal selection3(f132)

OFF

ON

3

∼ 15

-

-

-

-

Ex.: FE07 data when both the RY and OUT terminals are ON: 0003H

BIT15

BIT0

0

0 0

0

0 0

0

0 0

0

0 0

0

0 1

1

FE06:

FE07:

0

0

9

3

0

0

0

0

Advertising