02_NVspec_ver202e_pdf.xls 4_Network Variables

11

Request All Off

network input SNVT_switch nviAllOff;

This input network variable is used for the emergency Off of the indoor unit and all ventilation.

Valid Range

value field : not used

state field : 0 = Emergency Off of indoor unit and ventilator

: Else = not used

Default Value

The default value is determined by the state of the air conditioner (indoor unit).
This variable becomes value = 0 until the value is updated after the power supply of LM-AP.

WLN01-1023(Ver2.02)

- 19 -