02_NVspec_ver202e_pdf.xls 4_Network Variables
11
Request All Off
network input SNVT_switch nviAllOff;
This input network variable is used for the emergency Off of the indoor unit and all ventilation.
Valid Range
value field : not used
state field : 0 = Emergency Off of indoor unit and ventilator
: Else = not used
Default Value
The default value is determined by the state of the air conditioner (indoor unit).
This variable becomes value = 0 until the value is updated after the power supply of LM-AP.