VEGA VEGASON 71 - 1 … 75 - 1 User Manual

Page 33

Advertising
background image

Measurement, relay output

71 - 1 … 75 - 1

33

Programming example for tendency determination, e.g. 8 cm / min.

Coordination as described on page 28

Mode for relay output 1 ............................................

• select mode 0 - 44 in MODEFIELD
• program figure 4 in PARAMETER FIELD
• then store with STO-button

Tendency determination for relay output 1 ...............

• select mode 0 - 45 in MODEFIELD
• program e.g. 008.0 (cm / min.) in PARAMETER

FIELD

• then store with STO-button

After programming as above the relay output reacts
as follows:

with reducing rate of level change

8 cm / min.

> 8 cm / min.

Tendency determination (continuation)
relating to reducing level
example for relay output 1

Requirement:
-

enquire mode 4 (parameter 4) in mode 0 - 44

-

program the value of the required tendency
determination in mode 0 - 45

Procedure:
-

relay is not operated

-

if the level reduces quicker than programmed in
mode 0 - 45, the relay energizes

-

if the filling speed is the same or lower than the
given value, the relay de-energizes again

Note
(for raising or falling tendency determination)

If in case of fluctuating product surfaces of small
values are given for the tendency determination, is
useful to program an additional integration time.

Uncontrolled and undesired operation of the relay
output is then suppressed.

Same procedure for relay output 2 … 4, using asso-
ciated modes, see page 32.

Example as guideline:
at tendency determination < 10 cm / min.
recommended integration time: 10 … 30 secs.

With < 10 cm / min. the response time of the
tendency determination can be several minutes.

11

9

10

11

9

10

Advertising