Data transmitter 795, Appendix – Xylem 795 MJK Data Transmitter User Manual

Page 50

Advertising
background image

50

M795GB0503

Data Transmitter 795

SW ver. 830434

Dimensions:

185 x 240 x 115 mm (h × w × d)

Power supply:

230 / 115 V AC or 12 / 24 V DC

Emergency power:

Built-in accumulator for monitoring of power supply and emergency communication.
Kapacitet for ca. 3 nødopkald pr. opladning á 12 timer.

Power consumption:

15 VA (Approx.)

Temperature range:

- 20 … + 60 °C

Material, housing:

Polystyrol

Material, lid:

Makrolon

Enclosure:

IP 65

Ur:

Real time clock with built-in battery backup

Kommunikation

Telephone / fax:

Hayes compatible, auto dial, auto answer, 2400 / 4800 baud

GSM / GPRS:

900 / 1800 MHz GSM / GPRS modem

UHF:

Data radio via RS 232 port

APL / owned lines:

RS 485 for owned lines (multidrop)

Accuracy:

< ± ½ % for analogue inputs

CE:

EN50081-1, EN50082-1

Appendix

A

Appendix

A1

Technical specifications

A4

Dimensions

A2

Number of signals available

Number of possible signals on a standard Data Transmitter 795

I/O

Limit relays

Counters

Time counters

Alarms

Analoge indgange

4

8

8

8

8

Digitale indgange

8/12/16

8/12/16

8/12/16

8/12/16

Digitale udgange

8/4/0

Antal i alt

20

8

16/20/24

16/20/24

16/20/24

Alle værdier overføres som i dag, i går og totalværdier.

Analogue inputs:

0/4 - 20 mA or 0 - 1 V DC. Input voltage = 50

Ω.

Digital inputs:

8 / 12 / 16 DI, passive with common negative pole, max. 24 V DC. (Optocoupler with 10 k

serial resistor)

Trig voltage: < 1 V DC = Off, > 10 V DC = On, pulse length > 100 ms.

Digital outputs:

0 / 4 / 8 DO, voltage free relay contacts, max. 1 A v. 24 V DC / 0,5 A v. 48 V AC.

Digital I/O:

Total 16 DI + DO

Data communication:

2 x ports (RS 485 with item no. 204570 built-in)

A3

Inputs and outputs

Advertising