Xylem 795 MJK Data Transmitter User Manual

Page 9

Advertising
background image

9

M795GB0503

Data Transmitter 795

SW ver. 830434

3

Electrical mounting

Data Transmitter 795 must not be mounted in

explosion hazardous areas!

Data Transmitter 795 must not be connected to

the power supply before all connections are

made.

Remove the terminal lid and the front panel to
gain acces to all terminals.

3.1

Power supply

Data Transmitter 795 can be supplied from both
230 V AC and 24 V DC.

Terminal:

Designation:

Protective ground

N

230 V AC neutral

L

230 V AC live

-

24 V DC negative

+

24 V DC positive

Please note, that 24 V DC will not be available on
the terminals marked '24 V DC forsyning' unless
the Data Transmitter is fed from the mains.

3.2

In- and output signals

Data Transmitter 795 is delivered in 3 different I/O
variants; 4AI / 8DI / 8DO, 4AI / 12DI / 4DO and
4AI / 16DI respectively.

Specifications:

DI:

Passive with common negative, max. 24 V DC.
(Optocoupler med 10 k

serial resistor)

Trig voltage: < 1 V DC = Off, > 10 V DC = On,
pulse length > 100 ms.

DO: Voltage free relay contacts,

max. 1 A @ 24 V DC / 0,5 A @ 48 V AC.

AI:

0/4 - 20 mA or 0 - 1 V DC.
Input impedance = 50

Ω.

DI 1 +

DI 2 +

DI 3 +

DI 4 +

DI 1/2/3/4 common -

DI 5 +

DI 6 +

DI 7 +

DI 8 +

DI 5/6/7/8 common -

AI 1 +

AI 1 -

AI 2 +

AI 2 -

AI 3 +

AI 3 -

AI 4 +

AI 4 -

Rx for RS232 to 704

Tx for RS232 to 704

DO 1

DO 2

DO 3

DO 4

DO 1/2/3/4 common -

DO 5

DO 6

DO 7

DO 8

DO 5/6/7/8 common -

Shield for RS232 to 704

Signal ground for RS232 to 704

24 V DC out +

24 V DC out -

3.2.1 I/O terminals, 8 DI/8 DO/4 AI

Advertising