Controls, Troubleshooting, Figure 15 figure 14 – Bray 6P P_P Series User Manual

Page 12

Advertising
background image

Adjustment – Poppet Seat

Balance Pressure A/M Adjustment

NOTICE

The Poppet Seat Adjuster is factory set and sealed

before the positioner is shipped. Do not adjust

Auto / Manual default setting (Automatic) as shown.

Troubleshooting

Positioner does not respond to the input signal

1. Check the supply pressure to the actuator. The

supply must be at least 40 psi / 2.7 Bar / 0.27 MPa

2. Check if input signal is properly supplied to the

positioner. The signal range should be 3-15 psi.

3. Check if the positioner’s nozzle (5) has been

blocked. If the nozzle has been blocked by any

substances, please contact your local

Bray distributor for a replacement.

4. Check if feedback shaft has been adjusted

properly and engaged to actuator pinion.

The pressure of OUT 1 reaches exhausting
pressure level and does not come back down

1. Check Auto/Manual (A/M) switch. For proper

operation it must be in the “A” position.

2. Check for a gap or damage between the nozzle

(5) and the flapper (13). If damaged, please con-

tact your local Bray distributor.

Hunting occurs

• Check if feedback springs (15) have been dis-

placed.

• Hunting may occur when the positioner is

attached to a very small capacity actuator (ex:

Bray Series 92/93 size 48). In such case, install

an output orifice for OUT 1 and OUT 2 per the

following steps.
1. Remove Pilot Valve Assembly (Figure 2).
2. Remove the O-ring from OUT 1 and OUT 2

port, install orifice in and reinstall the O-ring

to OUT 1 and OUT 2 again. When mounting

the output orifice, pay attention not to let dust

or debris enter the orifice (Figure 16).

3. If hunting does not stop after installing the

output orifice, please contact your local

Bray distributor.

Actuator only operates Open or Closed

1. Check tubing connection
2. Check cam direction

Linearity is too low

1. Check if Zero and Span has been properly adjusted.
2. Check if supply air pressure level is stable from

the regulator. If the level is unstable, replace the

regulator.

O-ring

Orifice Diameter

Orifice

OUT 1

OUT 2

O-ring

Orifice Diameter

Orifice

OUT 1

OUT 2

Bray

®

is a registered trademark of BRAY INTERNATIONAL, Inc.

© 2013 Bray International. All rights reserved.

OM-6P-001 11-2013

A Division of BRAY INTERNATIONAL, Inc.

13333 Westland East Blvd. Houston, Texas 77041

281/894-5454 FAX 281/894-9499 www.bray.com

R

CONTROLS

Figure 15

Figure 14

A/M

Automatic/ Manual

Poppet Seal

Adjuster

A/M

A/M

Bray Series 6P

Operation and Maintenance Manual

Advertising