Sig-error, Configuration.of.signal.level.fault.detection – Burkert Type 8693 User Manual
Page 160
160
Start-up and operation of the
position controller Type 8693
25.4. SIG-ERROR -
configuration of signal level fault detection
The
SIG-ERROR function is used to detect a fault on the input signal.
fault detection
Fault detection can be selected at 4 – 20 mA and with a Pt 100 signal.
4 – 20 ma
Fault with input signal ≤→3.5 mA (± 0.5 % of end value, hysteresis 0.5 % of end value)
pt 100
Fault with input signal 225 °C (± 0.5 % of end value, hysteresis 0.5 % of end value)
If other signal types are selected or if process controllers are not activated, the respective menu branch is
hidden. If this configuration does not allow either of the two fault detections,
not available is indicated in
the selection menu.
SIG.ERROR
ENTER
SP/CMD Input
ENTER
EXIT
PV Input
ENTER
Signal fault detection
Process set-point value / nominal
position
Signal fault detection
Process actual value
Figure 100: Operating structure SIG-ERROR-8693
english
Type 8692, 8693