. other.malfunctions, Other malfunctions – Burkert Type 8693 User Manual
Page 217
217
Maintenance and troubleshooting
49.1.2. error messages while the X.TUNE function is running
Display
Causes.of.error
remedial.action
X.TUNE locked
The
X.TUNE function is blocked
Input access code
X.TUNE
ERROR 1
No compressed air connected
Connect compressed air
X.TUNE
ERROR 2
Compressed air failed during Autotune Check compressed air supply
X.TUNE
ERROR 3
Actuator or control system deaeration
side leaking
not possible, device defective
X.TUNE
ERROR 4
Control system aeration side leaking
not possible, device defective
X.TUNE
ERROR 6
The end positions for
POS-MIN and
POS-MAX are too close together
Check compressed air supply
X.TUNE
ERROR 7
Incorrect assignment
POS-MIN and
POS-MAX
To determine
POS-MIN and POS-MAX , move
the actuator in the direction indicated on the
display.
Table 59:
Error messages X.TUNE, Type 8692
49.2. Other malfunctions
Problem
Possible.causes
remedial.action
POS = 0 (when CMD > 0 %) or
POS = 100 %, (when CMD < 100 %)
Sealing function (
CUTOFF) has
been unintentionally activated
Deactivate sealing function
Table 60:
Other Malfunctions, Typ 8692
english
Type 8692, 8693