Warning, Leak testing – Detroit Radiant Products Company FA Series User Manual

Page 17

Advertising
background image

17

FA

Series

Leak Testing

Always leak test final gas assembly for gas leaks according to the procedures outlined in NFPA 54 and
all local codes and/or Standards.

For leak testing on pressures below ½” PSI

Before leak testing, close the field installed manual shut off valve shown on Figure 3.1 on the supply
line to isolate the gas valve from the pressure.

NOTE: All factory installed gas connections have passed an approved leak test.

For leak testing on pressures above ½” PSI

When leak testing with pressures above ½” PSI (14 inches W.C.), the unit must be isolated from the
supply pipe. Close the field installed manual shut off valve, disconnect the supply line to the unit, and
temporarily cap the supply line for testing purposes.

WARNING

!

Use a soap solution or equivalent for leak testing. Never test for leak with an open
flame. Failure to comply could result in personal injury, property damage or death.

Sediment

Trap

1/8-in. NPT Test

Connection (Plugged)

Shut Off

Ground Joint Union

Gas Supply Line

3-in.

Minimum

Flow of

Gas

To Unit

Figure 3.1

Recommended Hardware – Manual Shut Off and Sediment Trap

WARNING

!

Gas pressures to the appliance controls must never exceed 14 inches W.C. (1/2”
PSI). Supply pressures greater than 14” W.C. can damage the controls, resulting in
personal injury, property damage, or death.

3.0

Installation

Gas Supply Installation Instructions

Leak Testing

Advertising