Troubleshooting Guide

Do the burners

ignite?

Yes

Continued from page 42.

Do the burners

stay lit?

Yes

Does the air

motor fan turn

on approx. 30

seconds after

ignition?

Yes

Does the heater

stay on until the

call for heat ends?

Yes

Troubleshooting ends.

For more information, contact

your local representative or the

factory for further assistance.

No

Is the gas supply

valve to the heater in

the “on” position?

Turn on gas supply

line.

Yes

Check inlet pressure to the heater. Is it within

the minimum and maximum allowable range

as per the rating plate?

No

Yes

Adjust inlet pressure.

No

No

Do the burners light

and then shut off

immediately (within

1-2 seconds)?

Check inlet pressure

and limit switches.

Yes

Does the burner stay on for approximately

8-10 seconds, and then shut off?

Check circuit board for

flash codes. Consult

factory.

No

No

Yes

No

Does the circuit board send 120

VAC to the air movement fan after

approx. 30 seconds after ignition?

Yes

Is the motor dirty, obstructed, or

damaged, inhibiting rotation?

No

Verify wires are not

damaged. Check flash

codes, and then replace

circuit board.

No

Check motor starter capacitor.

Replace or repair.

Clean fan, remove obstruction, or

replace damaged parts.

Yes

No

The heater can shut down or stay on due to:

• Limit switch opening.
• Pressure switch opening.
• Improper grounding.
• Faulty control device.
• High winds.
• Taking combustion air from the attic.
• Dirty environment.
• Fluctuating gas pressure.