General Tools and Instruments CA10 User Manual

Page 10

Advertising
background image

The table below the figure shows the normal measurement result for each of
the four parameters. It also lists possible causes of, and remedies for, abnormal
results.

10

Parameter

Impedance of
live and neutral
conductors
(Z-L and Z-N)

Impedance of
ground
conductor (Z-E)

Normal
Measurement
Result

<0.15

Ω/m for

14AWG conductor

<0.1

Ω/m for

12AWG conductor

<0.03

Ω/m for

10AWG line

<1

Ω for personnel

safety

<0.25

Ω for

equipment safety

Actual Result

Impedance is too
high

Impedance is
too high

Possible Cause
of Abnormal
Result

Circuit is overloaded

Conductor is too thin
for circuit length
and/or circuit’s
current rating

High impedance
point(s) in circuit or
breaker box

Conductor is too thin
for circuit length
and/or circuit’s
current rating

High impedance
point(s) in circuit or
breaker box

Remedy

Redistribute circuit load

Replace wiring with
heavier-gauge conductors
suitable for circuit’s rating

Visually inspect all
connection points to detect
or rule out loose
connections and defective
outlets. If none are
apparent, locate points of
high impedance using an
infrared thermometer (IRT)
to detect their heat, or a
voltmeter to detect
excessive voltage drops
across parts. Repair or
replace defective
wiring/parts.

Replace wiring with
heavier-gauge conductors
suitable for circuit’s
rating

Visually inspect all
connection points to detect
or rule out loose
connections and defective
outlets. If none are
apparent, locate points of
high impedance using an
infrared thermometer (IRT)
to detect their heat, or a
voltmeter to detect
excessive voltage drops
across parts. Alternatively,
run the Z-L and Z-N
impedance tests on the
hot and neutral conductors;
if one conductor produces
a much higher reading
than the other, it is
defective. Repair or
replace defective
wiring/parts.

Advertising