SPECIFICATIONS

Parameter or Component

Measurement

Measurement

Resolution

Range

Accuracy

Line Voltage

85 to 265VAC

±1% of reading ± 0.2V

0.1V

Peak Voltage

121 to 374VAC

±1% of reading ± 0.2V

0.1V

Line Frequency

45 to 65Hz

±1% of reading ± 0.2Hz)

0.1Hz

Voltage Drop

0.1 to 99.9%

±2.5% of reading ± 0.2%

0.1%

Load Voltage

10 to 265V

±2.5% of reading ± 0.2V

0.1V

Neutral-to-Earth Voltage

0 to 10VAC

±2.5% of reading ± 0.2V

0.1V

Live, Neutral and

0 to 3

±2.5% of reading ±0.02

0.01

Ground Line Impedance

>3

NA

RCD Trip Time

1 ms to 6.5 sec.

±1% of reading ± 2 ms

1 ms

RCD Trip Current

30 to 37mA

±1% of reading ± 0.2mA

0.1mA

GFCI Trip Time

1 ms to 6.5 sec.

±1% of reading ± 2 ms

1 ms

Display

Backlit 2.4 in. (61mm) diagonal LCD

Test Cable

12 AWG diameter, 12 in. (305mm) long

Auto Power Off Trigger

30 minutes of inactivity

Display Backlight Duration

30 seconds

Operating/Storage

32° to 122°F (0° to 50°C) ) @ <80% RH

Temperature

Dimensions

7.6 x 3.1 x 1.5 in. (193 x 78 x 39mm)

Weight (Without Batteries)

10.4 oz. (295g)

Power Source

Six “AAA” batteries

OPERATING & MAINTENANCE TIPS

REPLACING THE BATTERIES

When the

(low battery) icon appears on the top line of the display, it’s time

to replace the unit’s six “AAA” batteries. Follow the instructions on p. 5 for
opening and closing the battery compartment and installing the batteries.

HOUSEKEEPING HINTS
DO NOT expose the CA10 to:

• Direct sunlight
• High humidity or temperatures (above 104°F/40°C during operation or

140°F/60°C in storage)

• Corrosive or explosive gas
• Excessive dust
• Strong mechanical vibration or stress (dropping, for example) or

electromagnetic radiation