NetworkAIR Rack Air Removal Unit Installation

Connect the power supply

1. Set the fan speed selector to OFF.

2. Using one of the supplied power cords, connect the female end to the "A" input socket on the

inside of the unit. Plug the male end into a power-protected socket. Ensure that there is adequate
power for the fans to run at 100% (230V 4 A). The UPS in the rack must be sized properly to
power this unit.

3. To provide redundant power to the unit, use the "B" input socket to connect to a second source

of protected power.

4. Attach the cord retainer to lock the cords in place.

Warning

Use the Rack Air Removal Unit only with a 3000 watt UPS or higher. The UPS
should not be loaded above 80% when using the Rack Air Removal Unit.

Note

Cords may be bundled and tie-wrapped to provide clearance for other components.