The filter-drier inside the unit removes acid, particulates, and moisture from
refrigerant during the recovery function. To provide adequate contaminant
and moisture removal, the filter-drier must be replaced after every 150 lbs.
(68 kg) of refrigerant recovered. The following will appear in the display:

Use the following steps to replace the filter-drier.

NOTE: For maximum unit performance, use only No. 34430 SPX/ROBINAIR
filter-drier. To avoid service delays, keep extra filter-driers on hand. Refer to
the Replacement Parts

section of this manual.

1. Plug the power cord into a correct voltage outlet, and turn the unit on.

2. Verify the service hoses are NOT connected to a vehicle.

Replacing the Filter-drier

CHANGE FILTER

Control Panel

3. On the control panel, open both panel valves.

4. Press the Mode key until RECOVER XX.XX displays on the screen.

5. Press the Start/Stop key.

6. Watch the low-side gauge. When the gauge pressure reaches 10 in. Hg

(34 kPa) vacuum, close both panel valves.

7. Turn the unit’s power switch off.

8. Remove the unit’s power cord from the outlet.

I

O

Start/Stop

Key

Low-Side

Gauge

High-Side

Gauge

Oil Drain

Valve

Valves shown closed

Mode

Key

Display

Screen

ISV Pressure
Gauge

Up

Arrow

Down
Arrow

Oil Inject

Button

Low-Side Panel

Valve

High-Side

Panel Valve

ISV
Temperature
Display

ON/OFF
Power Switch

Temp/Pressure
Chart

Advertising