Ez-zone, Watlow ez-zone, Pm integrated controller – Watlow EZ-ZONE PM Integrated Controller User Manual

Page 16: Chapter 1 overview

Advertising
background image

Watlow EZ-ZONE

®

PM Integrated Controller

13

Chapter 1 Overview

EZ-ZONE

®

PM Integrated Model 1/8 and 1/4 DIN System Diagram

With 6 Digital I/O (slot D), Without Communications (slot E)

Input

Function

Output

Function

off, heat, cool

alarm, retransmit,

duplex or event

EZ-ZONE PM Integrated 8

th

DIN System Diagram

With 6-digital I/O (slot D), Without Comms Card (slot E)

Analog Input 1

none, Thermocouple, RTD (100Ω,

1kΩ), Thermistor 5kΩ, 10kΩ, 20kΩ,

40kΩ) Process (V, mV, mA) or 1k

Potentiometer

PID Controller,

Limit, or

Current Trans-

former Sense

(CT)

Slots B

(Optional)

PID

Controller

(Optional -

Ramp/Soak max

4 files, 40 steps)

Slots A

(Optional)

Input Sensor

Output 2

none, 15A NO-ARC, switched dc,

5A mechanical relay (form A), or

0.5A SSR (form A)

Analog Input 2

none, CT, Thermocouple, RTD (100

Ω, 1kΩ), Thermistor 5kΩ, 10kΩ,

20kΩ, 40kΩ) Process (V, mV, mA)

or 1k Potentiometer

6 - Digital

Inputs / Outputs

Slot D

(Optional)

Power Supply

100 to 240Vac

20 to 28 Vac

or 12 to 40Vdc

Modbus

Address 1 - 247

Standard Bus

Zone Address

1 - 16

Supervisory &

Power Board

Slot C

EIA-485 Communication

Standard Bus

(optional Modbus RTU)

RUI, EZ-ZONE

Controllers, PLC, PC

or HMI

Output Status

LEDs

5 6

1

3

2

4

Zone

Address

LEDs

Channel

Indicates Zone

Address & Channel

Indicates I/O

Status

8

7

Input Sensor

If limit, this output

must be limit

Output 1

none, switched dc/open collector, 5A

mechanical relay (form C), process

(V, mA), or 0.5A SSR (form A)

off, heat, cool

alarm or event

Output 3

none, switched dc/open collector, 5A

mechanical relay (form C), process

(V, mA), or 0.5A SSR (form A)

off, heat, cool

alarm, event or limit

off, heat, cool

alarm, retransmit,

duplex or event

Output 4

none, 15A NO-ARC, switched dc,

5A mechanical relay (form A), or

0.5A SSR (form A)

off, heat, cool

alarm or event

off, heat, cool

alarm or event

Digital Input (or Output) 7-12 (optional)

Programmable Functions

Digital Output (or Input) 7-12

(optional) none, switched dc

Digital Input (or Output) 5 & 6 (optional)

Programmable Functions

EZ Key 1 & 2

Programmable Functions

- None

- Limit reset

- Idle set point

- Tune

- Alarm clear, request

- Silence alarm

- Manual/auto mode

- Control mode

- Remote set point

enable

- Lock keypad

- Force alarm

- TRU-TUNE+

®

disable

- Loop & alarms off

- Profile disable

- Profile hold/resume

- Profile start

- Profile start/stop

- Restore user settings

- Event inputs

- Math

Digital Output (or Input) 5 & 6

(optional) none, switched dc

Note:

Number of inputs and outputs and various combinations of the same will vary

depending upon part number; see ordering matrix for more detail.