Limit menu – Watlow EZ-ZONE PM Integrated Controller User Manual

Page 82

Advertising
background image

Watlow EZ-ZONE

®

PM Integrated Controller

79

Chapter 6 Setup Page

Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus Rela-

tive

Address

CIP

Class

Instance

Attribute

hex (dec)

Pro-

fibus

Index

Param-

eter ID

Data

Type

&

Read/

Write

[Lim]
[`Set]

Limit Menu

[`L;Sd]
[ L.Sd]

Limit (1)

Limit Sides

Select which side or sides

of the process value will

be monitored.

[both]

Both (13)

[high]

High (37)

[LoW]

Low (53)

Both

Instance 1

Map 1 Map 2

688

728

0x70 (112)

1

5

40

12005 uint

RWES

[`L;hy]
[ L.hy]

Limit (1)

Limit Hysteresis

Set the hysteresis for the

limit function. This de-

termines how far into the

safe range the process

value must move before

the limit can be cleared.

0.001 to 9,999.000°F or units

0.001 to 5,555.000°C

3.0°F or

units

2.0°C

Instance 1

Map 1 Map 2

682

722

0x70 (112)

1

2

41

12002 float

RWES

[SP;Lh]
[SP.Lh]

Limit (1)

Set Point High Limit

Set the high end of the

limit set point range.

-1,999.000 to 9,999.000

9,999.000 Instance 1

Map 1 Map 2

696

736

0x70 (112)

1

9

42

12009 float

RWES

[SP;Ll]
[SP.LL]

Limit (1)

Set Point Low Limit

Set the low end of the

limit set point range.

-1,999.000 to 9,999.000

-1,999.000 Instance 1

Map 1 Map 2

698

738

0x70 (112)

1

0x0A (10)

43

12010 float

RWES

[`Lh;S]
[ Lh.S]

Limit (1)

Limit High Set Point

**

Set the high process

value that will trigger

the limit.

-1,999.000 to 9,999.000°F or

units

-1,128.000 to 5,537.000°C

0.0°F or

units

-18.0°C

Instance 1

Map 1 Map 2

686

726

0x70 (112)

1

4

39

12004 float

RWES

[`LL;S]
[ LL.S]

Limit (1)

Limit Low Set Point

**

Set the low process

value that will trigger

the limit.

-1,999.000 to 9,999.000°F or

units

-1,128.000 to 5,537.000°C

0.0°F or

units

-18.0°C

Instance 1

Map 1 Map 2

684

724

0x70 (112)

1

3

38

12003 float

RWES

[SFn;A]
[SFn.A]

Limit (1)

Source Function A **

Set the source for the

limit reset function.

[nonE]

None (61)

[`dio]

Digital I/O (1142)

[`FUn]

Function Key (1001)

None

Instance 1

Map 1 Map 2

- - - -

748

0x70 (112)

1

0x0F (15)

- - - -

12015 uint

RWES

[`Si;A]
[ Si.A]

Limit (1)

Source Instance A **

Set the instance of the

function selected above.

1 to 12

1

- - - -

0x70 (112)

1

0x10 (16)

- - - -

12016 uint

RWES

[`lCr]
[ LCr]

Limit (1)

Limit Clear Request

**

Clear limit once limit

condition is cleared.

[`lCr]

Clear (0)

[ignr]

Ignore (204)

- - - -

Instance 1

Map 1 Map 2

680

720

0x70 (112)

1

1

- - - -

12001 uint

W

Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.

R: Read

W: Write

E:

EEPROM

S:

User

Set