IM 01E20C01-01E

4-8

4. WIRING

In case of explosion proof type for ATEX, FM, and
CSA certification, connect wiring as shown in the
figure below.

In case of the explosion proof type, the protective
grounding

of remote flowtube must be connected to

a suitable IS grounding system. In that case,
(functional grounding terminal) need not be connected.

I+

I–

CURRENT OUT

AL+

AL–

C

SA

A

B

SB

ALARM OUT

N/–

L/+

POWER SUPPLY

EX2

EX1

EXCIT ATION

P–

SI1+

SI2+

COM

P+

PULSE OUT

STATUS IN

SIGNAL

SO1+

COM

SO2+

STATUS OUT

AXFA11 Converter

AXFC Dedicated signal
cable

Converter

Remote

flowtube

F0416.EPS

SA

A

B

SB

C

EX1

EX2

Taping*

A

B

Taping*

C

EX1

EX2

* Individually tape and insulate the

shields corresponding to SA and
SB on the remote flowtube side.

Excitation cable

EX2

EX1

A

B

C

Remote flowtube

Figure 4.4.6

Wiring Diagram

(3) Connection with the Remote Flowtube

(General-Purpose Use, Submersible Type,
Size 500 to 1000 mm (20 to 40 in.))

Connect wiring as shown in the figure below.

I+

4-20mA out

Shortbar

I–

CURRENT OUT

AL+

AL–

C

SA

A

B

SB

ALARM OUT

N/–

L/+

POWER SUPPLY

EX2

EX1

EXCIT ATION

P–

SI1+

SI2+

COM

P+

PULSE OUT

STATUS IN

SIGNAL

SO1+

COM

SO2+

STATUS OUT

AXFA11 converter

Converter

Remote

flowtube

F040217.EPS

SA

A
B

SB

C

EX1
EX2

Taping*

A
B

Taping*

C

EX1
EX2

* Individually tape and insulate

the shields corresponding to SA
and SB on the remote flowtube
side.

Remote flowtube

EX2

Excitation
cable

EX1

A

B

C

AXFC dedicated
signal cable

Figure 4.4.7

Wiring Diagram

(4) Connection with the Remote Flowtube

(General-Purpose Use, Submersible Type,
Size 1100 to 2600 mm (44 to 104 in.))

Connect wiring as shown in the figure below.

I+

4-20mA out

I–

CURRENT OUT

AL+

AL–

C

SA

A

B

SB

ALARM OUT

N/–

L/+

POWER SUPPLY

EX2

EX1

EXCIT ATION

P–

SI1+

SI2+

COM

P+

PULSE OUT

STATUS IN

SIGNAL

SO1+

COM

SO2+

STATUS OUT

Shortbar

F040218.EPS

AXFA11 converter

Converter

Remote

flowtube

SA

A
B

SB

C

EX1
EX2

Taping*

A
B

Taping*

C

EX1
EX2

* Individually tape and insulate

the shields corresponding to SA
and SB on the remote flowtube
side.

Remote flowtube

AXFC dedicated
signal cable

EX2

EX1

A

B

C

Excitation
cable

Figure 4.4.8 Wiring Diagram

4.4.7

Connecting to External Instru-
ments

WARNING

Before wiring with external instrument, be sure to
turn off the power supply for AXFA11 converter
and any external instruments.

Connect the AXFA11 terminal to external instruments,
giving attention to the following points.

4 to 20 mA DC Current Output

Resistive Load Max. 1 k

Ω.

(When using BRAIN/ HART communication,
more than 250

Ω, less than 600 Ω).

Receiver

Instrument

AXFA11

l+

l-

F0417.EPS

Figure 4.4.9 4 to 20 mA DC Output Connection